GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 21
The panel generates fault sound.
Fault relay outputs.
Battery fault: The panel will reports battery fault if the battery voltage is lower than
21VDC or the internal resistance is higher than 0.7 ohm, and:
Light
FAULT
and
BATTERY FAULT
LED.
The LCD displays “BATTERY FAULT” or “BAT Resistance FAULT”.
The panel generates fault sound.
Fault relay outputs.
System fault: The panel will report system fault if its control CPU and circuit is in
fault and the panel cannot work normally.
It lights the
FAULT
and
SYSTEM FAULT
LED.
There is no display on the LCD.
The panel generates continuous alarm sound.
The keypad cannot be used.
After the fault is removed, the FACP has to be reset by rebooting.
Fault relay outputs.
Keypad fault: The panel reports keypad fault if its keypad circuit is in fault:
It lights the
FAULT
and
SYSTEM FAULT
LED.
The LCD displays “hardware fault”.
The panel generates continuous alarm sound.
Fault relay outputs.
The keypad cannot be used.
The FACP can monitor fire alarm.
After the fault is removed, the FACP has to be reset by rebooting.
Ground fault: When ground fault testing terminal J1 is shorted, the input or output
cable is grounded, and the FACP reports ground fault.
It lights the
FAULT
and
GROUND FAULT
LED.
The LCD displays GROUND. F.
The FACP generates fault sound.
Fault relay outputs.
Field device fault: If there is trouble with one of the field devices, the panel reports
fault with it, and
The panel lights the
FAULT
LED.
The corresponding LED on the zone indication panel flashes.
The panel generates fault sound.
Fault relay outputs.
The LCD displays the fault message.