GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 2
Preface EN 54 Information
GST-IFP8 Intelligent Fire Alarm Control Panel (FACP) complies with the
requirements of
EN 54-2 1997 + A1: 2006 and EN 54-4 1997 + A1: 2002 +
A2: 2006. In addition to principal requirements of these standards, the
panel conforms to the following optional requirements.
Option
EN 54-2 Clause
Indication
Alarm counter
7.13
Fault signals from points
8.3
Control
Delays to outputs
7.11
Dependencies on more than one alarm signal
7.12
Disablement of addressable points
9.5
Outputs
Output to fire alarm devices
7.8
Control of fire alarm routing equipment
7.9
Output to fire protection equipment
7.10
Test
Test condition
10
The power supply of GST-IFP8 FACP complies with EN 54-4
requirements.
EN 54-4 Clause
Power supply from the main power source
5.1
Power supply from the standby power source (battery)
5.2
Charger
5.3
Faults
5.4
In addition to functions required by EN54-2, the panel supports a number
of ancillary functions beyond En54-2. These are outlined below:
Ancillary Function
Section in the Manual
SP-E32PK Thermal Printer
3.2.2
RS232/USB Output
2.3 & 3.2.2
GST852RP Repeater Panel
3.3.6
GstDef2.1 Defining Tool
3.4
Fire Alarm Output
4.4.3.3
RS485 Output
2.3 & 4.4.3.5
EN 54
√
EN 54
√
EN 54
N/A