GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 2
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved Fire cables
Recommended Cable Length
≤1000m
2.3.2 RS232 Communication Loop
Connecting with a PC for running graphic monitor system through a DB9 port or
USB port.
Connecting with XS1 of P-9935Modbus Communication Card, Modbus RTU
protocol communication can be executed with the third party Modbus system.
Connecting with computer with graphic monitor center (GMC) system through
REPEATER (A, B) port. It also provides a RS485 port.
Recommended Wiring:
RS232: Standard RS-232 interface. The 2
nd
pin (for sending data), the 3
rd
pin
(for receiving data), and the 5
th
pin (ground) are connected with PC through
three-core screened cable
(Note: the length of cable should be shorter
than 3m;
the screening
layer and computer’s enclosure should be
earthed).
USB: Standard USB printer cable. The length of cable should be less than 3m.
RS485 Port:
Recommended Wiring (subject to local installation codes):
GST fire cable
Vencroft Gold and Platignum
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved Fire cables
Recommended Cable Length
≤1000m
2.3.3 CAN Communication Loop (non-loop circuit/loop circuit)
P-9965 CAN Network Card and P-9965A CAN Network Card Loop Type are
optional.
NETWORK
(
non-loop type, even I+, I-
)
:
Communication cable for connecting with
up to 240 network FACPs from GST
(
I+ corresponds to CAN_L, I- corresponds to
CAN_H
)
. CAN_H and CAN_L are connected to CAN_H and CAN_L of the next
FACP.
NETWORK
(
loop type, even I+, I-, O+, O-
)
:
Communication cable for connecting
with up to 100 network FACPs from GST.
(
I+ corresponds to CAN_L2, I-
corresponds to CAN_H2, O+ corresponds to CAN_H1, O- corresponds to
CAN_L1. CAN_H1 and CAN_L1 are to be connected with CAN_H2 and CAN_L2 of
the next FACP; CAN_H2 and CAN_L2 are connected with CAN_H1 and CAN_L1
of the previous FACP.
)
Recommended Wiring (subject to local installation codes):
Vencroft Gold and Platignum