GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 15
Monitor and control network is connected shown in Fig.4-8d through P-9935 Modbus
Communication Card.
CRT Line
P-9935
Modbus
Card
RS485
Other
Modbus
System
Modbus interface
Fig.4-8d
Repeater loop connection is shown in Fig. 4-8e.
Fig. 4-8e
4.5 Connection Inspection and Device Registration
4.5.1 Connection Inspection
Check the circuit connected with the FACP. Measure the insulation resistance between
loops and between loops and ground, which should be more than 20MΩ. Measure the
load of detection loops, which should be more than 1kΩ. The resistance between cables
of ALARM ROUTING, OUTPUT TO SOUNDER and OUTPUT TO FPE should be equal
to the end-of-line resistance.
4.5.2 Device Registration
Step 1: Set the FACP into commission state. Press
SYSTEM SETUP
and enter system
setup menu. Choose
“3 WORKING STATE SETUP”, you can then set the FACP as
commission or monitoring state (Fig. 4-9).