GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 3
Chapter 1 Product Introduction
GST-IFP8 Intelligent Fire Alarm Control Panel (FACP) is designed to comply with EN
54-2 standard. With simple installation, operation, and easy maintenance, it is
applicable in fire alarm system to have the following features:
It controls at most 140 zones, each of which has its own alarm and fault/disable
LEDs and a label. Every zone can be programmed to associate with fire alarm and
fire suppression devices.
Maximum 8 Class A loops, each with up to 242 addressable devices. It is compatible
with a series of addressable GST products, which are intelligent sounder strobe
(I-9403) complying with EN 54-3, rate of rise and fixed temperature heat detector
(I-9103) complying with EN 54-5,
photoelectric smoke detector (I-9102) complying
with EN 54-7, intelligent manual call point (I-9202) complying with EN 54-11,
intelligent reflective beam detector (I-9105R) complying with EN 54-12, input and
output module (I-9300, I-9301) complying with EN54-18, and loop isolator (C-9503)
complying with EN54-17.
The LCD can display 15 lines in total and 40 characters each line, assisting the 17
LEDs in displaying important information individually.
The memory does not lose data even if power source is accidentally removed.
Automatically prompting operation steps for every alarm device and for smoke
exhaust and fire suppression devices by field programming.
Sounder strobe interface provides 1A/24V output, compatible with GST conventional
sounder strobe (C-9403) designed according to EN 54-3.
RS232/USB interface enables the FACP to communicate with PC.
RS485 interface enables networking.
P-9935 Modbus Communication Card is optional to communicate with the third party
system through Modbus Protocol.
P-9945RP Repeater Card is optional to connect the FACP with repeater panels.
P-9945A RS485 Network Card Loop Type is optional to form ring-type fire alarm
supervisor network.
P-9965A CAN Network Card Loop Type is optional to form ring-type fire alarm
supervisor network.
P-9965 CAN Network Card is optional to form loop fire alarm supervisor network.
Printer Module Kit is optional to print operation or fire messages
P-9904 USB Printer Interface Card is optional to connect an external USB printer for
printing operation or fire messages.
Содержание GST-IFP8