
GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 36
6.3.1.1 Device Setup
Choosing
“1” on the screen of Fig. 6-21 will enter the screen for setting up devices.
Fig. 6-22
In Fig. 6-22, inputting loop number and device address followed by
ENTER
, then the
device type, zone, attribute and note text can be entered on the screen shown in Fig.
6-23 below.
FAR:OK FPE:DIS OTS:OK 20:44:30
*******************************************
*DEVICE SETUP*
Zone (1-999)
:
001
Device Type:01-OPTICAL SMOKE
Attribute(0-6):1
Text(40 Byte):
Loop:01 Address(1-242):001
Fig. 6-23
Choosing
ENTER
after programming of one detector will enable the setup of the next
one.
FAR:OK FPE:DIS OTS:OK 20:44:30
*******************************************
*DEVICE SETUP*
Loop:01 Address(1-242):001
Loop
number
Device
address
Содержание GST-IFP8
Страница 1: ......