GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 6
P-9935 Communication card
P-9935 Modbus Communication card
The monitor & control card provides RS232, RS485 or USB port for
communication with PC, so that the FACP can connect with urban fire alarm
and monitor network, or the central monitor and control system in a building for
integrated graphic control.
REPEATER card (RS232/RS485/USB card)
P-9945RP Repeater Card
REPEATER card provides RS485 port for connecting with GST repeater
panels.
There is a decimal rotary switch on each loop board, communication board and
network board, for setting the channel number of the board. The loop board has
dual channels, and after the rotary switch set the number of the first channel, the
second channel will automatically get its number by adding one to the number of
the first. The numbers of the loop board, communication board and network board
can be mixed.
3.3 Periphery Devices
3.3.1 A Series of Intelligent Fire Detectors
GST-IFP8 can connect with a series of fire detectors, such as I-9102, I-9103, and
I-9105R. The detectors mounted in the protected area transmit monitoring message to
the FACP through Class A loop. Every detector has its own address with which the
FACP can monitor the alarm, fault, and normal status of the detectors.
3.3.2 Modules
GST-IFP8 can connect with I-9300 Addressable Input Module and I-9301 Addressable
Single I/O Module. I-9300 module is used for receiving normally open digital signal from
fire protection device and transmitting the signal back to the fire alarm control panel.
I-9301 module is for connecting fire protection devices that need to be controlled by the
FACP, such as smoke valve, fresh air valve, and damper valve. It can also receive
answer signal from these devices.
3.3.3 Loop Isolator
Loop Isolator can remove the shorted part of loop from the whole system to ensure
normal operation of other devices and to ascertain the location of the part in fault. After
the fault is repaired, the loop isolator can automatically reset the removed part into the
system.
3.3.4 Manual Call Points
A series of manual call point (such as I-9202) can be connected to the loop of GST-IFP8.
When fire is confirmed manually, press the glass on the MCP, alarm signal can be sent
to the FACP. After receiving the alarm signal, the FACP will show the number and
location of the MCP, and sound alarm.