level. In addition, the algorithm is continuously learning from the previous cycles to reach the
desired CO
₂
as precise as possible.
The settings “room volume” and “CO
₂
flow” are used as a starting point.
The minimum and maximum fan speeds for the CO
₂
period can be set individually. It is
recommended to keep the airflow low to avoid wasting CO
₂
. In addition, the room should be
well sealed.
To ensure an even distribution of CO
₂,
good air circulation inside the room should be
maintained.
Here the CO
₂
function can be enabled or
disabled.
Set the desired CO
₂
concentration here.
(ppm = parts per million)
Set the room volume here.
Unit: (length * height * width) m*m*m = m³
Enter the flow set on the CO
₂
armature or
specified for your CO
₂
generator.
Unit: l/min = litres / minute
The table below can be used as rough
reference for the CO
₂
flow.
Room volume
CO
₂
flow
< 10 m³
8 l/min
10-20 m³
10 l/min
20-50 m³
15 l/min
50-100 m³
20 l/min
> 100 m³
25 l/min
Enter the specified maximum air flow of
your exhaust fan(s) according to the
manufacturer.
With this setting the controller knows how
much air is extracted from the room in a
certain period of time at the current fan
speed. The CO
₂
amount is increased
accordingly.
Set the desired temperature for CO
₂
mode.
When this temperature is exceeded, the
fan speeds will be increased as long the
following MIN/MAX settings allow.
CO2 function
C
F
ON at daytime
BC
Concentration
F
CO2
C
1200ppm
BC
Room volume
C
F
18.0m
l
3
BC
Flow
F
CO2
C
10.0l/min
BC
Exhaust @ 100
A
F
1450m3/h
BC
Set desired
F
tempCO2
32
.0
A
C
BC