Instruction manual 1.0.0 rev1 en  

GROW

BASE  

 

 

19

 

Current intake fan speed = 40% 

With a pressure sensor 

PRES

SENSE

, the speed of the intake fans is controlled by a PID 

controller to always maintain the desired negative pressure in pascal (Pa). 

In this case the value “negative pressure %” provides a limitation of the intake fan speed. 
(upper boundary) 
Example: Negative pressure in %: 5% 
The intake fans will never run faster than “current exhaust fan speed” minus 5% even if the 
currently measured negative pressure is above the desired negative pressure (Pa).

 

EC fans are turned off if they are driven below 10%. 

The fan speed of AC fans can’t be decreased without limits. When a certain value is undercut the 
fan would not run reliable. How low the fan speed can be reduced, is depending on the particular 
AC fan. 
To avoid driving the AC fan to low, a value for switch off is defined. This value can be set in 
section “advanced setup” at “intake AC turnoff” and “exhaust AC turnoff”. 
If at “intake/exhaust MIN/MAX” a value below this setting is entered, the message “AC intake/ 
exhaust OFF<##!” is displayed. In order to not turn off the corresponding fan, the value for 
“intake/exhaust MIN/MAX” must be grater then the corresponding value “AC turnoff”. 
If only EC fans are used, “intake AC turnoff” and “Exhaust AC turnoff” can be set to 10% to disable 
the message described above. 
 
The minimum fan speed can’t be greater than the maximum fan speed. 
Examples: 

 

If for “exhaust MAX” a value smaller than “exhaust MIN” is entered, “exhaust MIN” is 
set to the same value as “exhaust MAX” by the controller. The message “Fan MIN 
updated” is displayed. 

 

If for “exhaust MIN” a value greater than “exhaust MAX” is entered, “exhaust MAX” is 
set to the same value as “exhaust MIN”  by the controller. The message “Fan MAX 
updated” is displayed. 

 

Set the maximum fan speed of the exhaust 
fans. This fan speed will never be exceeded. 
Separate values for day and night are 
available. 

 

Set the minimum airflow of the exhaust 
fans. Separate values for day and night are 
available. 
Pleas pay attention to the explanations 
regarding “AC turnoff” at the beginning of 
this chapter. 

 

Ensure that the fan is still rotating at 
the set minimum fan speed and the 

Set exhaust    

F

 

day MAX

C

  100

A

BC

 

Set exhaust    

F

 

day MIN

C

   50

A

BC

 

Содержание GROWBASE

Страница 1: ...winnerstr 46 60388 Frankfurt Germany Mail info growcontrol de Web www growcontrol de Instruction Manual GROWBASE Multifunctional digital climate controller with timer functions and CO control For AC a...

Страница 2: ...observe the relevant information Store this instruction manual and make it accessible to all users Ensure that you include this instruction manual when handing over the device to third parties With k...

Страница 3: ...detail 13 7 1 Info level 13 7 2 Climate 15 7 3 CO2 16 7 4 Ventilation 18 7 5 Timing 21 7 6 Lights 22 7 7 Advanced setup 23 7 8 System setup 23 7 9 Multifunctional Out 26 7 10 Firmware update 26 8 Appe...

Страница 4: ...well as plug connections for their proper condition prior to each use Check the proper status of all parts connected to the device Do not use the device if it is damaged Do not pull on the cables to...

Страница 5: ...of fire if the device is used improperly or these instructions for use are ignored Never use the device near highly flammable substances Operation Warning The device is only intended for the purpose d...

Страница 6: ...to a power socked on the controller It should be connected to a standard power socked that is always on The speed control and switch off is done with the signal from the corresponding RJ45 jack Warni...

Страница 7: ...ors is able to control the CO level in the grow room with a CO sensor CARBSENSE connected is able to calibrate the connected CO sensor ensures a constant negative pressure in the grow room avoiding th...

Страница 8: ...the included screws dowels and drilling template Provided that the sizing of the connected utilities is appropriate and the fresh air temperature is sufficiently low The tolerance is related to the re...

Страница 9: ...0V dimming of lights and Multifunctional Out 5 4 RJ45 jack for exhaust EC fan 5 RJ45 jack for intake EC fan 6 5xRJ45 jack for sensors and PowerExtenders 7 USB A Port for firmware updates 8 11 Programm...

Страница 10: ...nctions according to your requirements 4 Connect the EC fans to the RJ45 jacks labelled intake and exhaust 4 5 using a suitable cable 5 Connect other accessories sensors lights with 0 10 1 10V etc to...

Страница 11: ...ev1 en GROWBASE 11 Menu overview Setup Info 1 Start Climate setup 2 System setup 8 Advanced setup 7 Cancel return home Save return home Save apply Lights setup 6 Timing setup 5 Ventilation setup 4 CO2...

Страница 12: ...d and the previous screen will be displayed To jump from the level Info directly to the level Setup press the rotary switch a bit longer and then release it while an Info screen is displayed Longer th...

Страница 13: ...ng the operation condition is displayed This screen is the home screen It shows the current temperature Temp and relative humidity RH This screen shows the current CO concentration detected by the CO...

Страница 14: ...e percent value represents the power transmitted to the fan The rpm value represents the fan s actual rpm The rpm value is not transmitted from all EC fans The rpm value can only be displayed if the c...

Страница 15: ...switch while this screen is displayed Climate In this section all setpoints desired values associated with temperature or humidity can be configured For each temperature or humidity setpoint a separa...

Страница 16: ...This will extract the humidity from the grow room given that the humidity of the fresh air is lower when inside the grow room This function is independent of whether a humidifier or dehumidifier is co...

Страница 17: ...eight width m m m m Enter the flow set on the CO armature or specified for your CO generator Unit l min litres minute The table below can be used as rough reference for the CO flow Room volume CO flow...

Страница 18: ...ve pressure can be set Separate values for day and night are available The factory settings are a good starting point for many setups Considerations for the optimum settings are Reasonable noise of th...

Страница 19: ...g is entered the message AC intake exhaust OFF is displayed In order to not turn off the corresponding fan the value for intake exhaust MIN MAX must be grater then the corresponding value AC turnoff I...

Страница 20: ...ue of 10 is set this means that the intake fan will always turn 10 less compared to the exhaust fan With a pressure sensor connected The setting limits the speed of the intake fan compared to the exha...

Страница 21: ...Event Timer times event start and event duration can be set e g event 1 start 14 30 hh mm event 1 duration 00 10 00 hh mm ss One or more events can be assigned to one power socket e g function out 1 e...

Страница 22: ...or 1 10V input For lights with a 0 10V input the brightness control as well as the turnoff is done with the 0 10V signal The mains supply of the lights doesn t have to be switched off in order to swi...

Страница 23: ...low the fan speed can be reduced is depending on the particular AC fan To avoid driving the AC fan to low a value for switch off is defined In order to not turn off the corresponding fan the value for...

Страница 24: ...average minimum maximum It defines which value is used for the corresponding function For these values settings are available RH Humidity captured by sensors RH T T Temperature captured by sensors RH...

Страница 25: ...fter a successful transfer of the filter value a message similar to the Apply calibration In order to restore all factory settings choose OK and confirm by pressing the rotary switch Please note that...

Страница 26: ...The sockets of GROWBASE are not optimized for switching LED luminaires or energy saving lamps To guarantee that the luminaires are completely switched off the 4th socket of the GROWBASE PRO controller...

Страница 27: ...rmat The firmware file has to be on the top level of the folder structure It may not be saved inside a folder The number of firmware files saved on one USB drive is limited to 20 files The name of a f...

Страница 28: ...ive pressure value If the value is too high the speed of the supply air fan will oscillate With a small value the negative pressure control reacts less responsive to changes in the currently measured...

Страница 29: ...er is following a PD or a P algorithm Hysteresis humidifier Set the hysteresis for the control of a humidifier here The hysteresis determines how often the humidifier is switched on and off and how ex...

Страница 30: ...connect lights with an 0 10 1 10V input or DC relays contactors use a suitable cable available as an accessory The assignment of the RJ45 jack labelled Lights 0 10V is shown in the following figure l...

Страница 31: ...mation only and has no influence on the control or function Function colour EC standard Pin RJ45 10V red 3 0 10V yellow 4 GND 0V blue 5 Pulse rpm white 6 Table 1 What to do if there are problems Probl...

Страница 32: ...r exhaust air AC The socket Multifunctional Out 4 is not switched on The 2nd power cable for the 4th socket is not connected Connect both power cables to the controller Table 2 Technical data Dimensio...

Страница 33: ...ng this period is to repair or replace the defective part or product with a comparable part or product at GrowControl s sole discretion Except for such replacement the sale or other handling of this p...

Страница 34: ...ry Version 1 0 0 rev1 en created on 26 10 2021 English translation Version 1 0 0 created on 13 06 2020 First release German version Refers to firmware version 5045 0 00 04 and higher Version 1 0 0 rev...

Страница 35: ...Instruction manual 1 0 0 rev1 en GROWBASE 35 V1 0 0 rev1 en GrowControl Excepting errors and changes...

Отзывы: