Initial use
Warning!
If “intake AC” or “exhaust AC” mode is selected for an “Multifunctional Out 1-3“output, only
standard duct fans may be connected. Other devices may be damaged in the modes “intake
AC” or “exhaust AC”. When shipped, the functions of “Multifunctional Out 1 and 2” are set to
“intake AC” and “exhaust AC”.
1.
Place the humidity and temperature sensor
(14)
in an appropriate position inside the grow
room, usually at the top ends of your plants. Please use the sensor hanger supplied
(13)
. The
sensor should not be exposed directly to the fog stream of the humidifier. Connect the
humidity and temperature sensor to any of the RJ45 jacks labelled “In/Out”
(6).
2.
Connect the mains plug
(12)
to the power supply (regular power socket).
3.
Set the function of the “Multifunctional Out 1-5” outputs and set up all other functions
according to your requirements.
4.
Connect the EC fans to the RJ45 jacks labelled “intake” and “exhaust”
(4)
,
(5)
using a suitable
cable.
5.
Connect other accessories (sensors, lights with 0-10/1-10V etc) to the RJ45 jacks.
6.
Connect appropriate devices to the other power outputs.
For AC fans, we recommend disconnecting the mains plug
(12)
first. Subsequently, connect
the fans to the corresponding power sockets on the controller and then reconnect the mains
plug.
Always ensure that the maximum output power of the individual outputs is not exceeded.
Please find further information on the device’s label or section 10 (Page 32) of this manual.
Avoid exposing the temperature and humidity sensor to moisture and humility above 95% RH
as the sensor may become damaged.
EC fans have their own power supply cable, which should be plugged to a regular power
socket (always on). It should not be connected to a power socket on the climate
controller. The fan’s rpm control and turn off is made via the signal cable from the RJ45
jack on the controller to the EC fan.