GREE
Multi Variable Air Conditioners Indoor Unit
169
4.7 Two-way Cassette Type Indoor Unit
NOTICE!
The following steps are specific for GMV-ND09TS/A-T(U) units. For other units, the assembly
and disassembly procedure is similar except the numbers of centrifugal fans and motors.
Removal of Fan Motor
Precondition: The power supply has been disconnected.
Step
Diagram
Operation Procedure
(1) Remove
the grille
Slip the fasteners on the panel,
open the grille, remove it.
(2) Remove
the line
connecting
to the
motor.
Use a screwdriver to unscrew
the electric box cover.
Remove from the master board
the line connecting to the motor
and remove the tie.
(3) Remove
the
motor/Rem
ove the
motor from
the support
Use a screwdriver to unscrew
the motor/volute casing
subassembly and joint slack.
Loosen the fasteners of the
motor, remove the motor from
the support.
Remove the volute casing
subassembly as well.
(4) Remove
the
centrifugal
fan
Remove the volute casing.
Use a hexagon to unscrew the
centrifugal fan, remove it from
motor axle.
(5) Replace the
motor with a
new one.
Assemble units based on the
reverse order of this procedure
and power on the units for test.
Содержание CM100N1480
Страница 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Страница 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Страница 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Страница 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Страница 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Страница 266: ...JF00302921...