3.15.3 Installation Notice
(1) Installation dimension (refer to the outline dimension in the figure).
(2) Installation foundation.
(3) Make sure the top hanging rod, ceiling and building structure have sufficient strength to
withstand the weight of unit.
(4) Installation site and environment.
1) Keep the unit from insolation and rain.
2) Keep the unit from fire, flammable objects, corrosive gap or exhaust gas.
3) Please reserve ventilation space.
4) Please reserve sufficient space for maintenance.
5) Please take proper measures to reduce noise and vibration.
(5) Electrical installation of unit.
All electrical installation must be done by professionals according to national and local laws and
regulations.
The unit must be grounded reliably. Please connect wire according to the wiring diagram on the unit.
3.15.4 Selection of Air Switch and Power Cord
Model
Power Cord Size
Air Switch
Capacity
(A)
Minimum Sectional
Area of Ground Wire
(mm
2
/AWG)
Minimum Sectional
Area of Power Cord
(mm
2
/AWG)
GMV-ND30PLS/C-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND36PLS/C-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND42PLS/C-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND48PLS/C-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
3.16 Installation of 360°Air Discharge Compact Cassette Type
Indoor Unit
3.16.1 Outline and Installation Dimension
Содержание CM100N1480
Страница 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Страница 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Страница 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Страница 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Страница 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Страница 266: ...JF00302921...