GREE
Multi Variable Air Conditioners Indoor Unit
65
In parameter query status, signals of the remote controller are invalid.
4.1.5 User Parameter Settings
User parameters can be set in power-on or power-off status.
(1) Press and hold the “FUNCTION” button for five seconds. The temperature area displays “C00”.
Press and hold the “FUNCTION” button for another five seconds to enter the wired controller
parameter setting interface. The temperature area displays “P00”.
(2) Select a parameter code by pressing “
” or “ ”. Press the “MODE” button to switch to
parameter value settings. The parameter value blinks. Adjust the parameter value by pressing
“ ” or “ ” and then press the “ENTER/CANCEL” button to complete settings.
(3) Press the “ENTER/CANCEL” button to return to the upper-level menu till quitting parameter
settings.
The user parameter setting list is as follows:
Table 4.2 User Parameter Setting List
Parameter
Code
Parameter
Name
Parameter Range
Default
Value
Remark
P10
Master IDU
settings
00: does not change the
master/slave status of the
current IDU
01: sets the current IDU
to master IDU
00
After the IDU connected with the current
wired controller is successfully set to master
IDU, "MASTER" on the wired controller is on.
P11
Infrared
connection
settings of
wired controller
00: disabled
01: enabled
01
This setting can only be enabled through the
master wired controller.
When the infrared remote receiving function
of the wired controller is disabled, neither the
master nor slave wired controller can receive
remote signals. The wired controllers can
only be operated by pressing.
P13
Wired controller
address
settings
01: master wired
controller
02: slave wired controller
01
When two wired controllers simultaneously
control one or more IDUs, the two wired
controllers should use different addresses.
The slave wired controller (address: 02) does
not have the unit parameter setting function
except its own address settings.
P14
One wired
controller
controls
multiple IDUs
quantity
settings
00: disabled
01-16: number of indoor
units
01
This value is set based on the number of
connected IDUs.
If the current value is inconsistent with the
actual number of group-controlled IDUs, an
“L9” fault may occur.
Содержание CM100N1480
Страница 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Страница 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Страница 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Страница 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Страница 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Страница 266: ...JF00302921...