GREE
Multi Variable Air Conditioners Indoor Unit
119
3.12.3 Selection of air switch and power cord
Model
Power Supply
Circuit
Breaker
Capacity (A)
Minimum Sectional
Area of Ground Wire
(mm
2
/AWG)
Minimum Sectional
Area of Power Cord
(mm
2
/AWG)
GMV-ND09A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND12A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND18A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND24A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND30A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND36A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND42A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND48A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND54A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
3.13 Installation of AHU-KIT
3.13.1 Outline and installation dimension
Size of control box for GMV-N12U/A-T(U) / GMV-N24U/A-T(U) / GMV-N48U/A-T(U) /
GMV-N96U/A-T(U) and GMV-N192U/A-T(U):
Unit: mm(inch)
380(15)
30
6(
12
)
111(4-3/8)
24
8(
11
-1
/8
)
30
6(
12
)
24
0(
11
-1
/8
)
20
0(
7-
7/
8)
334(13-1/8)
4-Φ9
360(14-1/8)
Содержание CM100N1480
Страница 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Страница 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Страница 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Страница 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Страница 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Страница 266: ...JF00302921...