GREE
Multi Variable Air Conditioners Indoor Unit
109
Below are dimensions of A, B, C, etc. for different models:
Unit: mm(inch)
Models
A
B
C
D
H
GMV-ND09ZD/A-T(U)
GMV-ND12ZD/A-T(U)
GMV-ND18ZD/A-T(U)
1220
(48)
225
(8-7/8)
1158
(45-5/8)
280
(11)
700
(27-9/16)
GMV-ND24ZD/A-T(U)
GMV-ND30ZD/A-T(U)
1420
(56)
245
(9-5/8)
1354
(53-5/16)
280
(11)
700
(27-9/16)
GMV-ND36ZD/A-T(U)
GMV-ND42ZD/A-T(U)
GMV-ND48ZD/A-T(U)
1700
(66-15/16)
245
(9-5/8)
1634
(64-5/16)
280
(11)
700
(27-9/16)
3.8.2 Installation Space
Floor type
Unit: mm(inch)
>600
(23-5/8)
>1000(39-3/8)
>300(11-3/4)
>1
50
0
(5
9)
>600
(23-5/8)
Ceiling type
Unit: mm(inch)
>3
00
(1
1-
3/
4)
>1500(59)
>200
(7-7/8)
>2
30
0
(9
0-
1/
2)
>600
(23-5/8)
>600
(23-5/8)
3.8.3 Installation Notice
The unit shall be installed by the professional personnel according to this installation instruction
to ensure proper use.
Please contact the local Gree appointed service center before installation. Any malfunction
caused by the unit that is not installed by the Gree appointed service center would probably not
be dealt with on time because of the inconvenience of the business contact.
It should be guided under the professional personnel when the air conditioner unit is moved to
other place.
The unit shall be installed in accordance with national standards or local regulations.
Only qualified personnel can carry out installation work, please contact with local dealer before
installation.
Содержание CM100N1480
Страница 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Страница 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Страница 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Страница 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Страница 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Страница 266: ...JF00302921...