GREE
Multi Variable Air Conditioners Indoor Unit
73
Parameter
Code
Parameter
Name
Parameter Range
Default Value
Remark
P21
Corrected value
of environment
temperature
sensor of IDU
(for cooling,
dehumidifying,
and air supply)
-15 to +15
Temperature
sensor of unit:
0°C;
temperature
sensor of wired
controller: 0°C
Press “ ” or “ ” to add or
reduce by 1°C.
P22
Corrected value
of environment
temperature
sensor of IDU
(for heating, fast
heating, and air
warming)
-15 to +15
Temperature
sensor of unit:
-2°C;
temperature
sensor of wired
controller: 0°C
Press “ ” or “ ” to add or
reduce by 1°C.
The temperature sensor of
unit and the temperature
sensor of wired controller
share the same corrected
value.
In heating mode, corrected
value of temperature sensor
of unit = corrected value of
temperature sensor of wired
controller - 2°C.
P32
Capacity
adjustment
function of IDU
-40% to +40%
00
Press " " or " " to add or
reduce by 10%.
P35
Factory setting
recovery for user
functions
00: invalid
01: valid
00
Select "01" and then press
and hold the
“ENTER/CANCEL” button to
restore the factory settings for
user functions (factory setting
recovery fails if remote
shielding is valid).
P36
Factory setting
recovery for
engineering
settings
00: invalid
01: valid
00
Select "01" and then press
and hold the
“ENTER/CANCEL” button to
restore the factory status for
engineering settings (factory
setting recovery fails if remote
shielding is valid).
P40
Prevention for
heat collection
00: disabled
10: 10 seconds
20: 20 seconds
30: 30 seconds
40: 40 seconds
50: 50 seconds
60: 60 seconds
00
It indicates the number of
seconds for enabling the
low-level fan every 15
minutes.
P42
Project number
settings of IDU
1-255
Automatically
generated upon
the initial
system
operation
In “P42” status, press the
“MODE” button to enter the
setting menu. The project
number blinks in the timer
area. Press “ ” or “ ” to
adjust the project number.
Press the “ENTER/CANCEL”
button to confirm settings and
return to the upper-level
menu.
P45
One-key project
number reset for
IDU
00: invalid
01: valid
00
When it is set to "01", the
wired controller initiates an
IDU project number reset
command.
Содержание CM100N1480
Страница 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Страница 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Страница 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Страница 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Страница 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Страница 266: ...JF00302921...