GREE
Multi Variable Air Conditioners Indoor Unit
64
Parameter
Code
Parameter Name
Parameter
Range
View Method
C11
Indoor unit quantity
query in
one-to-many mode
1-16
Timer area: displays the number of IDUs controlled by the
wired controller.
C12
Outdoor
environment
temperature query
-
Timer area: displays the temperature value of the environment
temperature sensor of the master ODU.
C17
Indoor relative
humidity query
20-90
Operation method:
In “C17” status, press the “MODE” button to enter the indoor
relative humidity query interface. Press “▲” or “▼” to switch
the IDU SN.
Display mode:
Temperature area: displays the project number of IDU (project
numbers are arranged from small to large).
Timer area: displays the relative humidity value.
If the HBS network consists of only one IDU, the timer area
directly displays the IDU relative humidity value in the “C17”
interface.
C18
Indoor unit project
number query in
the communication
network
1-255
Operation method:
In “C18” status, press the “MODE” button to enter the IDU
project number query interface. Press “▲” or “▼” to switch the
IDU SN.
Cancellation method:
If users quit the "C18" query interface within 20 seconds, the
project number display is cancelled.
If the query interface is quit after 20 seconds upon timeout,
press the “ON/OFF” button in power-on or power-off status to
cancel the project number display.
The method for cancelling the project number display on any
wired controller in the network is the same as
.
Display mode:
Temperature area: displays the SN of the current IDU (project
numbers are arranged from small to large).
Timer area: displays the project number of the current IDU.
Each IDU/wired controller in the network displays its own
project number (the wired controller circularly displays project
numbers of IDUs every three seconds from small to large).
C20
Fresh-air IDU
outlet temperature
query
-9 to 99
Operation method:
In “C20” status, press the “MODE” button to enter the fresh-air
IDU temperature query interface. Press “▲” or “▼” to switch
the IDU SN.
Display mode:
Temperature area: displays the project number of the current
IDU (1-16, project numbers are arranged from small to large).
Timer area: displays the fresh-air IDU outlet temperature.
If the HBS network consists of only one IDU, the timer area
directly displays the fresh-air IDU outlet temperature in the
"C20" interface.
C23
Inquiry of the
version of wired
controller
-
Display mode:
Display in timer zone: version of the wired controller (display
on the right)
Note:
Version of the wired controller refers to the version of the
program of the wired controller
The version number doesn’t have decimal points. It’s an
integral number.
NOTICE!
In parameter query status, "FAN", “TIMER”, "SLEEP", and "SWING" are invalid. By pressing
the “ON/OFF” button, users can return to the main interface but not power on/off the unit.
Содержание CM100N1480
Страница 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Страница 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Страница 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Страница 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Страница 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Страница 266: ...JF00302921...