GREE
Multi Variable Air Conditioners Indoor Unit
81
(2) In "C00" status, continuously press the “MODE” button for three times to enter engineering
parameter query.
(3) Select a parameter code by pressing “▲” or “▼”.
(4) Press the “SWING/CANCEL” button to return to the upper-level menu till quitting parameter
query.
(5) For the engineering parameter query list of the XK79 wired controller, refer to the engineering
parameter query list in XK46 engineering parameter query.
Note:
In parameter query, the function of "SWING/CANCEL" on the XK79 wired controller is equivalent
to the function of “ENTER/CANCEL” on the XK46 wired controller.
4.3.5 Engineering Parameter Settings
Engineering parameters can be set in power-on or power-off status.
(1) Press and hold the “FUNCTION” button for five seconds. The temperature area displays “C00”.
Continuously press the “MODE” button for three times, and then press and hold the
“FUNCTION” button for another five seconds to enter the wired controller engineering
parameter setting interface. The temperature area displays “P00”.
(2) Select a parameter code by pressing “▲” or “▼”. Press the “MODE” button to switch to
parameter value settings. The parameter value blinks. Adjust the parameter value by
pressing“▲” or “▼” and then press the “SWING/CANCEL” button to complete settings.
(3) Press the “SWING/CANCEL” button to return to the upper-level menu till quitting parameter
settings.
For the engineering parameter setting list of the XK79 wired controller, refer to the engineering
setting query list in XK46 engineering parameter settings.
Note:
In parameter settings, the function of "SWING/CANCEL" on the XK79 wired controller is
equivalent to the function of “ENTER/CANCEL” on the XK46 wired controller.
4.4 Engineering Application Functions Operated through the YV1L1
Remote Controller
The YV1L1 remote controller provides all engineering application functions. It is set to common type
by default upon factory departure. It can use engineering application functions only after being set to
professional type. The following only describes engineering application functions. For other user
operation functions, refer to the "Remote Controller Operating Instructions".
Method for setting the professional remote controller: Press "
" and "
" simultaneously in
power-off status. If "
" blinks for three times, it indicates that the setting succeeds.
Method for restoring the common remote controller: Press "
" and "
" simultaneously in
power-off status. If "
" blinks for three times, it indicates that the setting succeeds.
Содержание CM100N1480
Страница 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Страница 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Страница 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Страница 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Страница 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Страница 266: ...JF00302921...