Appendix I: Connecting a fire alarm system directly
to an eXentro fire/eVACuation panel
The eXentro fire alarm system interface is used for zoned eVACuation. If only automatic
eVACuation of ALL control is needed, one can connect the fire alarm system to an emergency
panel directly. For this connection between the fire alarm system and emergency panel, 2
relay contact closures (NO) are required; one to select the ‘All Zones’ input, which needs to
be triggered first to select the zones, and one to select ‘Start EVACuation’, which needs to be
triggered secondly (after the ‘All Zones’ input has been triggered) to start the eVACuation.
Appendix I:
Connecting a fire alarm system directly to an eXentro fire/evacuation panel
Switch to select
"all zones"
Switch to start
the alarm message