Engl
ish
8. Technical Specifications
11
*NOTE:
These specifications are applicable for all system components used in the eXentro
Voice Alarm system. At low temperatures LCD displays may suffer from 'blacked-out' screens!
Make sure to have an average temperature of about 20 degrees C. in the technical room.
**NOTE:
Max power consumption is measured with the maximum number of 4x4 cards installed
and maximum number of emergency panels connected.
8. Technical Specifications
Line Inputs (4 zone card)
4x Audio: 0 dB, balanced. Range: -90 to +6 dB
Line Outputs (4 zone card)
4x Audio, 1x Auxiliary, 1x Backup amp: 0 dB, balanced. Range: -90 to +6 dB
Amplifier inputs (4 zone card)
4x Zone amplifier / 1x Backup amplifier
Loudspeaker A/B outputs (4 zone card)
Each output (sum of A+B): 100 V/8 A max, minimum monitored load:
30 Watt @ 100 V
Microphone Inputs
2x Audio: 0 dB, balanced. Range: -90 to +6 dB (for emergency microphones)
External audio input
0 dB, balanced. Range: -90 to +6 dB
Alarm signal output
0 dB, balanced. Range: -90 to +6 dB
Emergency panel bus 1 & 2
48 Vdc / 500 mA max.(total available current for both connections)
THD
<0.2% (from line input to line output) / <0.2% (from emergency panel input
to line output)
Frequency response (0, -3 dB)
20 Hz - 18 kHz
Signal to Noise ratio
> 85 dB
Operating voltage
230 Vac (-15%/+10%) 50/60 Hz & 48 Vdc (-15%/+10%)
Maximum Inrush Current (230 Vac / 50 Hz)
0.3 A
AC Fuse (in AC mains entry)
0.5 A slow (2x), size: 5x20 mm
AC Fuse 'F1', secondary (on mother board)
2 A slow, size: 5x20 mm
DC Fuse 'F2' (on mother board)
0.5 A slow, size: 5x20 mm
Max Power consumption**
50 W (@ 230 Vac) / 1.5 A (@ 48 Vdc)
Idle power consumption
50 W (@ 230 Vac) / 1.0 A (@ 48 Vdc)
AC Heat Loss (in BTU/h)
Max.: 165
DC Heat Loss (in BTU/h)
Max.: 165
Dimensions (WxHxD)
482x88x350 (mm)
Weight (max)
2.5 kg
Operating temperature*
0 to 40 degrees C.
Humidity*
93% max.
Air pressure*
86 kPa to 106 kPa