310531 69
Module Internal Interface Signals
Analog Input
Signal Name
Connector / Pin
Signal Description
PrecisionFlo
Outlet Pressure
SIG = MS–C
COM = MS–B
Provides an input from the pressure transducer at the PrecisionFlo
metering valve outlet to the PrecisionFlo control assembly. This signal is
necessary for the module to control outlet pressure, and allows the
operator to monitor fluid pressure from the control pendant.
PrecisionFlo Inlet
Pressure
SIG= OP–K
COM = OP–L
(Optional) Provides an input from a pressure transducer at the inlet to
the PrecisionFlo metering valve. This allows the PrecisionFlo module to
monitor inlet pressure, and the user to view inlet pressure by using the
control pendant to enter AUTOMATIC mode and display pressures.
Tip Pressure
–––
–––
(Optional) Provides an input from a pressure transducer at the tip of the
dispense gun. Tip pressure can be used to detect bead skips in extru-
sion applications. The operator can view tip pressure by using the
control pendant to enter AUTOMATIC mode and display pressures.
Motor Tempera-
ture
SIG = MP–C
COM = MP–D
Provides an input from a thermistor temperature sensor mounted on the
metering valve motor. This input is used to detect excessive tempera-
ture rise in the motor. If an excessive temperature rise is detected, the
PrecisionFlo module signals a fault, places fault code 5 on the data bus,
and disengages the MCR to remove power from the PrecisionFlo drive
circuitry.