310531 35
Configuring the PrecisionFlo Module
Using Flow Mode
In flow mode, you enter the maximum flow rate re-
quired by the application. The PrecisionFlo module:
1.
Determines current flow rate.
2.
Calculates the outlet pressure required to obtain
the desired flow rate.
3.
Calculates a linear ratio of the robot’s analog input
voltage to the desired flow rate.
4.
Adjusts outlet pressure to maintain the desired
flow rate.
For example: When you enter the maximum flow rate,
the PrecisionFlo module analyzes fluid characteristics,
which are affected by factors such as viscosity and
ambient temperature, then determines the pressure
required to obtain the desired flow rate and adjusts the
pressure/flow relationship accordingly.
0
0
10
Flow Rate (cc/minute)
Volts
(Vdc)
Max.
Flow
Rate
Fig. 26
Flow mode: Analog voltage to flow rate ratio
To set flow calibration:
1.
Determine whether the PrecisionFlo module will be
using pressure mode or flow mode.
2.
If your PrecisionFlo configuration includes a flow
meter (A), determine the maximum flow rate
required by the application.
Fig. 27
A
3.
If your PrecisionFlo configuration does not include
a flow meter, determine the maximum outlet
pressure for your application.
Setting Flow Calibration
COMPONENT RUPTURE HAZARD
Never exceed the maximum air or fluid
working pressure rating of the lowest
rated component in the system. Over-
pressurization can cause component rupture and
serious bodily injury.
WARNING
There are 2 procedures for calibrating the flow. The
procedure you use depends on whether or not your
PrecisionFlo configuration has a flow meter connected
to the PrecisionFlo control assembly.
Calibration for Systems that have a Flow Meter
Connected to the Control Assembly
To calibrate the material flow:
1.
Make sure the CONTROL ON indicator is lit on the
control assembly. If not, press MASTER START/
STOP RESET on the control assembly, (24) in
Fig. 30.
2.
On the control pendant:
HOME
SETUP
FLOW CALIBRATION
You see:
––FLOW CALIBRATION––
Enter Maximum Operating
Flow Rate
xxxcc/min
3.
Place the dispensing device over a waste contain-
er.
NOTE: In the pressure mode, the volume component
is automatically disconnected.
Continued on the next page.