68 310531
Module Internal Interface Signals
Digital Input
Signal Name
Connector /
Pin
Signal Description
Temperature Fault
WIRE 1561
A temperature conditioning system can raise this signal to indicate an
over- or under-temperature condition to the PrecisionFlo module. The
activation of this signal will cause the PrecisionFlo module to place fault
code 24 on the data bus for transmission to the external controller
(unless volume data is currently being reported).
Control On
WIRE 1251
This signal is made high by the PrecisionFlo module Master Control
Relay (MCR) to indicate that power is applied to the PrecisionFlo drive
circuitry.
Flow Meter
+12 = FM –A
COM = FM–B
SIG = FM–C
Provide a pulse input to determine the actual volume dispensed. This
feedback is necessary to perform flow calibration, SPC calculations,
and Automatic Volume Compensation (AVC).
Digital Output
Signal Name
Connector /
Pin
Signal Description
Gun On
SIG = OP–E
COM = OP–B
This signal is raised by the PrecisionFlo module to actuate the solenoid
valve that opens the dispense gun. The PrecisionFlo module turns this
signal ON in response to a manual or external dispense request. This
signal is turned OFF to shut off the dispense gun.
MCR Enable
WIRE 1801
CR180
This signal is turned ON by the PrecisionFlo module to disable the
MCR in the event of a motor over-temperature fault. The disabled
MCR removes power from the PrecisionFlo motor drive.
Watchdog
WIRE 1761
CR176
This signal is turned OFF by the PrecisionFlo module processor to put
the module in a Dispenser System Stop condition. This occurs when
the processor halts due to an internal failure. The signal is normally
ON.
Closer
SIG = OP–E
COM = OP–B
This signal is turned on by the PrecisionFlo to release the positive
needle closing mechanism after the PrecisionFlo has stopped regulat-
ing and before the closing force current is removed from the motor.