GLX-RSS-2-300 WL Non-Contact Flow Meter
Device ID
Device ID
- Configures the device (slave) ID to be used on RS-485 interface protocols (Modbus RTU
or HS). Both protocols use request/response format and allow multiple instruments to be connected
on the same bus. When a remote master transmits the request message, it will use the device ID as
a device address. All instruments will receive the request, but only the instrument with the matching
device ID will answer to the received request.
Modbus settings
Modbus settings
- Configures the parity and number of stop bits used in communication. Parity is
used in serial communication for basic error detection. When parity is set to
None
, no parity is used,
and no error detection is possible on bit level. When parity is set to
Odd parity
, an additional bit is
added to the communication that will be set to 1 when there is an odd number of bits with value
1 in the 8-bit payload byte. Similarly, when parity is set to
Even parity
, an additional bit is added
to the communication that will be set to 1 when there is an even number of bits with value 1 in the
8-bit payload byte. Generally, all bytes on the receiver side where the parity bit is not matching the
message will be discarded. The default setting on most devices that use Modbus is even parity. Stop
bits are added to the end of each data byte transferred over serial communication, to allow pause
between two bytes. One or two bits may be used. The default setting is even parity and one stop bit.