SITEMANAGER 6
– Job definition:
For this configuration step, open the following menu:
The definition of events is important for emergency measures. Please note that these events refer to the alarm behaviour, but
not to the pre-alarms that appear in the monitoring.
Search for the following events:
Event: Alarm Analog Input 1:
Jobs assigned to this event determine what should happen when an alarm condition is reached.
The Counter Event: Alarm Analog Input 1 off
Jobs assigned to this event determine what should happen when the alarm state has been left.
Click
>
, to unfold the tab and get an overview of all configured jobs coming with this event:
Click
+
to open the Job configuration dialogue.
Note:
The jobs that can be executed are the same as those that can be triggered for the UPS events. This allows full integration of the
environmental control sensors into the warning and alarm behaviour. Please note that other sensors may provide different
setting options depending on their function. For more information, please refer to the CS141 user manual, available for
download at www.generex.de
Digital Inputs
– Assign a Job to an Event
Suchen Sie nach Alarm Digital Input