The following jobs are currently available
:
Log
Inserts a free definable message into the event log.
Email*
CS141 will send an email.
Email Trap*
CS141 will send Trap Mails
RCCMD Shutdown*
CS141 will transmit a shutdown signal to one or more RCCMD clients.
RCCMD Message*
CS141 will send an RCCMD message to one or more RCCMD clients.
RCCMD Execute*
CS141 will send a command to execute a custom file.
UPS Shutdown***
Turn off UPS
AUX**
CS141 will trigger external relays.
Buzzer**
If a buzzer is connected, CS141 can activate it by using this job.
RCCMD Trap*
CS141 will send an RCCMD trap message.
Send WOL
Wake On LAN - The CS141 will send so-called magic packet to a network device.
Send SMS**
If a GSM modem is connected, CS141 will be able to send SMS.
AUX: Switch Outlets***
As an example, the UPS can be instructed to disconnect the live outlets after a full discharge of
the batteries and run a time-delayed release to guarantee a minimum charge of the batteries..
WAKEUP
If two UPS are running in redundancy mode, this custom RCCMD command can be used to
withdraw an RCCMD shutdown command
*
Additional software may be necessary.
**
This feature may require additional equipment and accessories.
***
This function is only available to a limited extent: although some UPS systems fundamentally support the functionality,
they respond very differently to this job:
Some UPS systems accept and confirm this job, but ultimately decide themself about execution and timing.
UPS Shutdown definition
Why is the job UPS shutdown a little bit tricky?
A UPS performs a UPS shutdown to protect the batteries from a deep discharge. The UPS is physically shut down and turned
off. The time when a UPS performs this action or how it reacts to a triggered action by scheduler or via UPS functions already
varies even between the models within a manufacturer - in addition, each manufacturer uses its own definitions for to protect
batteries. But due to the fact the UPS has been physically turned off, counter events cannot be configured.
Configuring UPS Shutdown
Shutdown time in seconds
Defines how long the UPS should maintain operation before shutting down itself.
Restore time in seconds
When the main power supply is restored, the UPS waits for the pre-set value in seconds until it starts up again.
Type
With this setting the UPS will be turned off or turn on. Two different settings are possible:
1
The UPS switches off the outputs but remains in operation mode.
2
The UPS shuts down and turns off completely until the main power is restored.
How to use the job UPS Shutdown
This job cannot map both settings together.
Depending on the desired operation modes, at least two jobs are required.
As an example, it is possible to use different jobs to complete the following sequence:
-
Switch off outputs after 3 minutes
-
Shutdown the UPS after 4 minutes
-
Turn on the UPS 2 minutes after the main power supply is restored
-
Activate the outputs 15 minutes later