19
Model FL4000H
TEST
LAMP
FLASHING
READY
MODE
ANALOG
OUTPUT:
1.5 mA (3.5 mA
with HART)
LED FLASH
SEQUENCE:
Test Mode Active
(Sequence #7)
RELAY
SETTING:
Ready
ANALOG
OUTPUT:
16 mA
LED FLASH
SEQUENCE:
Test Mode Warning
(Sequence #8)
RELAY
SETTING:
Warning
ANALOG
OUTPUT:
20 mA
LED FLASH
SEQUENCE:
Test Mode Alarm
(Sequence #9)
RELAY
SETTING:
Alarm
ANALOG
OUTPUT:
4.3 mA
LED FLASH
SEQUENCE:
Ready Mode
RELAY
SETTING:
Ready
* USER SETTING VIA DIP SWITCH (0, 8, 10, OR 14 SEC) OR MODBUS (0 - 30 SEC)
** FACTORY PROGRAMMABLE
2 SEC.
**
TE
ST LAMP
C
O
NT
INUO
USLY F
L
ASHING
0
- 30 SE
C.*
4.2
5
MIN.
**
5 - 8 S
E
C
.
PHASE 0
PHASE 1
PHASE 2
PHASE 3
PHASE 4
PHASE 0
TEST LAMP IS POINTED ON FL4000
Latching?***
YES
Latching?***
YES
IGNORED MISUSE CONDITIONS
-
GROUND TEST WIRE
- HOLD TEST WIRE GROUNDED
- RESEND TEST MODE MODBUS COMMAND
-
TEST LAMP FLASHING IN TL103 MODE FOR
TL104 OR IN SWITCH POSITIONS 1-3 and 5
FOR Tl105 TEST LAMP
*** IF RELAY IS LATCHED DURING THE TEST MODE, IT MUST BE MANUALLY RESET
VIA RESET RELAYS LINE OR MODBUS COMMAND
Figure 7: Test Lamp Flashing Option (Auto-detection)
H
Содержание FL4000H
Страница 2: ...ii Model FL4000H This page intentionally left blank ...
Страница 8: ...viii Model FL4000H Figure 2 Mounting Instruction Figure 3 Wall Mounting Assembly ...
Страница 28: ...28 Model FL4000H Figure 16 Detector Mounting and Installation ...
Страница 61: ...61 Model FL4000H 6 2 Final Assembly Figure 26 FL4000H Cross Section View ...