71
Model FL4000H
Table 41: Detector Test Mode Initiation or/Detector Alarm Trigger with Test Lamp
Flame Detector
to Test
Rotary Switch
Setting
Maximum Distance
to Detector (ft)
Results
UV & UV/IR
Type V & VI
15
UV & UV/IR Type V & VI
triggers into alarm mode
FL3000
15
FL3000 triggers into alarm
mode
FL3001
35
FL3001 triggers into alarm
mode
FL3002
10
FL3002 triggers into alarm
mode
FL3100
20
FL3100 triggers into alarm
mode
FL3101
35
FL3101 triggers into alarm
mode
FL3102
10
FL3102 triggers into alarm
mode
FL3110
20
FL3110 triggers into alarm
mode
FL3111
35
FL3111 triggers into alarm
mode
FL3112
8
FL3112 triggers into alarm
mode
FL4000H
35 (High Sensitivity)
FL4000H enters test
mode
FL4000H
18 (Medium
Sensitivity)
FL4000H enters test
mode
FL4000H
8 (Low Sensitivity)
FL4000H enters test
mode