Xedge Chassis Systems
Xedge 6002 Chassis
032R440-000
Xedge 6000 Hardware
2-7
Issue 17
Installation & Setup Guide
Xedge 6002 System Management Connections
For local configuration and management of the switch, the RJ45 connector at the chassis front panel
provides local management access via an asynchronous terminal.
lists the pinouts for this
management port. To connect a terminal, perform the following steps:
1. Connect the terminal to the CRAFT connector of the Xedge 6002 chassis.
2. Set the terminal to the following parameters:
•
VT100 emulation
•
19,200 baud
•
8 character bits
•
No parity
•
No flow control
Note
The initial model of the Xedge PCL(1) slot controller is intended for operation only in the Xedge 6002 chassis
with the local management terminal set to 9600 baud. A later model of the Xedge PCL(2) is intended for
nonslot-0 use in any Xedge chassis with the terminal set to 19,200 baud.
Table 2-3
Xedge 6002 Craft Port Pinouts
Pin
Signal
1
--
2
--
3
RXD
4
--
5
GND
6
TXD
7
--
8
--