GE Reason Switches
Chapter 7
– Configuration
210
REASON SWITCHES-TM-EN-3
Unit:
indicates which unit should be used with Rate value
to limit traffic. Allowed values are kbps, Mbps, fps and
kfps;
o
Broadcast Frames
: indicates configuration to be applied when
frames are from and to broadcast hosts. Possible configuration is
as follows:
Enabled:
enable Broadcast Frames policing function at
the port. Checkbox selected means function enabled, and
checkbox empty means disabled;
Rate
: indicates rate to be applied on the storm policing
function at that port. Traffic rates at the port higher than
this field are not allowed if function is enabled. Allowed
values are integer values and limits depend on the Unit
used. Range of 100 to 1,000,000 is allowed when kbps or
fps units are used. Range of 1 to 32,000 is allowed when
Mbps or kfps units are used;
Unit
: indicates which unit should be used with Rate value
to limit traffic. Allowed values are kbps, Mbps, fps and
kfps;
o
Unknown Frames
: indicates configuration to be applied when
frames are from and to unknown hosts, that is, flooded frames
throughout the network. Possible configuration is as follows:
Enabled:
enable Unknown Frames policing function at the
port. Checkbox selected means function enabled, and
checkbox empty means disabled;
Rate:
indicates rate to be applied on the storm policing
function at that port. Traffic rates at the port higher than
this field are not allowed if function is enabled. Allowed
values are integer values and limits depend on the Unit
used. Range of 100 to 1,000,000 is allowed when kbps or
fps units are used. Range of 1 to 32,000 is allowed when
Mbps or kfps units are used;
Unit:
indicates which unit should be used with Rate value
to limit traffic. Allowed values are kbps, Mbps, fps and
kfps;
If one configuration
is desired to be applied at all ports, then the row “*” should be
used, that is, configuration done in the “*” row will be replied to all ports. Possible
configurations are as follows.
After one of the configurations described before is changed, there are buttons that
allow the user to save or discard the configurations.
o
Save
: save configuration at the Running Config;
o
Reset
: undo changes made locally at the Running Config.
Содержание T1000
Страница 2: ......
Страница 11: ...Figure 97 T1000 dimensions 298 Figure 98 S2020 and S2024G dimensions 299...
Страница 12: ......
Страница 41: ...Chapter 3 Hardware Design GE Reason Switches REASON SWITCHES TM EN 3 41 Figure 4 S2024G Switch...
Страница 103: ...GE Reason Switches Chapter 4 Functions REASON SWITCHES TM EN 3 103 Figure 64 Data Monitor Flow Network...
Страница 256: ......
Страница 274: ......