ASTAT XL User Manual
Fout! Stijl niet gedefinieerd.
46
DET-812
Description:
Slows the ASTAT XL's response to current imbalance, avoiding trips due to
momentary fluctuations.
5C – Undercurrent Delay
Range:
0:00 - 4:00 (minutes:seconds)
Default:
5 seconds
Description:
Slows the ASTAT XL's response to undercurrent, avoiding trips due to
momentary fluctuations.
5D – Instantaneous Overcurrent Delay
Range:
0:00 - 1:00 (minutes:seconds)
Default:
0 second
Description:
Slows the ASTAT XL's response to overcurrent, avoiding trips due to
momentary overcurrent events.
5E – Input A Trip Delay
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay between the input activating and the soft starter tripping.
5F – Input A Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay before an input trip can occur. The initial delay is counted from
the time a start signal is received. The state of the input is ignored until the
initial delay has elapsed.
5G – Frequency Delay
Range:
0:01 - 4:00 (minutes:seconds)
Default:
1 second
Description:
Slows the ASTAT XL's response to frequency disturbances, avoiding trips due
to momentary fluctuations.
8.4.6
6 Inputs
6A – Local/Remote
Options:
LCL/RMT Anytime
HAND/AUTO
button is always enabled.
LCL/RMT When Off
HAND/AUTO
button is enabled when the starter is off.
Local Control Only
All remote inputs are disabled.
Remote Control Only Local control buttons (
START
,
RESET
,
HAND/AUTO
) are
disabled.
Description:
Selects when the
HAND/AUTO
button can be used to switch between local
and remote control, and enables or disables the local control buttons and
remote control inputs.
The
STOP
button on the keypad is always enabled.
6B – Comms in Remote
Options:
Disable Control in RMT
Enable Control in RMT (default)
Description:
Selects whether the starter will accept Start and Stop commands from the
serial communication network when in Remote mode. The Reset and
Local/Remote Control commands are always enabled.
6C – Remote Reset Logic
Options:
Normally Closed (default)
Normally Open
Description:
Selects whether the ASTAT XL's remote reset input (terminals 58, 57) is
normally open or normally closed.
6D – Input A Function