ASTAT XL User Manual
Fout! Stijl niet gedefinieerd.
DET-812
19
5.7
Power Input and Output Configurations
5.7.1
Internally Bypassed Models (QLxxB0023D~QLxxB1000D)
Models QLxxB0023D ~ QLxxB0220D have power inputs at the top of the unit and outputs at the bottom
of the unit.
Internally bypassed models QLxxB0255D ~ QLxxB0425D have output busbars at the bottom of the unit
and input busbars at both the top and bottom of the unit. The AC supply can be connected 'Top in,
Bottom out' or 'Bottom in, Bottom out'.
Internally bypassed models QLxxB0500D ~ QLxxB1000D have input and output busbars at the top and
bottom of the unit. The AC supply can be connected 'Top in, Bottom out', 'Top in, Top out', 'Bottom in,
Bottom out' or 'Bottom in, Top out'.
QLxxB0023D~
QLxxB0105D
QLxxB0145D~
QLxxB0220D
QLxxB0255D~
QLxxB0425D
QLxxB0500D~
QLxxB1000D
1/L1, 3/L2, 5/L3
2/T1, 4/T2, 6/T3
1/L1 3/L2 5/L3
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
2/T1 4/T2 6/T3
1
5
6
1
4
.A
Status Graphs Logs
Exit
Enter
Menu
Local
Remote
Local
Ready
Run
Trip
Start
Reset
Stop
RemoteInputs
InputA
Start
Stop
Reset
Status Graphs
Logs
Exit
Enter
Menu
Local
Remote
Local
Ready
Run
Trip
Start
Reset
Stop
RemoteInputs
InputA
Start
Stop
Reset
Status Graphs
Logs
Exit
Enter
Menu
Local
Remote
Local
Ready
Run
Trip
Start
Reset
Stop
RemoteInputs
InputA Start
Stop
Reset
Status Graphs
Logs
Exit
Enter
Menu
Local
Remote
Local
Ready
Run
Trip
Start
Reset
Stop
RemoteInputs
InputA Start
Stop
Reset
5.7.2
Non-bypassed Model - QLxxX0255D
QLxxX0255D has dedicated bypass terminals at the bottom of the unit.
The bypass terminals are T1B, T2B, T3B.
15
6
13
.A
Status Graphs Logs
Exit
Enter
Menu
Local
Remote
Local
Ready
Run
Trip
Start
Reset
Stop
RemoteInputs
InputA Start
Stop Reset
1/L1
3/L2
5/L3
T1B
T2B
T3B
2/T1
4/T2
6/T3
5.7.3
Non-bypassed Models (QLxxX0360D~QLxxX1600D)
QLxxX0360D~QLxxX1600D have dedicated bypass terminals, on the input busbars. The bypass
terminals are L1B, L2B, L3B.
The busbars on non-bypassed models QLxxX0360D ~ QLxxX1600D can be adjusted for top or bottom
input and output as required. All units are manufactured top in/bottom out.
NOTE
For models QLxxX0360D ~ QLxxX1600D to be UL compliant, these must be mounted Top In,
Bottom Out or Top Out, Bottom In. See
UL Compliant Installation
on page 14 for more
information.