This function is ideal for remote installations using 2-wire control in Auto mode. If the 2-wire start
signal is present after an auto-reset, the ASTAT XL will restart.
9A – Auto-Reset Action
Options:
Do Not Auto-Reset (default)
Reset Group A
Reset Group A & B
Reset Group A, B & C
Description:
Selects which trips can be auto-reset.
9B – Maximum Resets
Range:
1 - 5
Default:
1
Description:
Sets how many times the soft starter will auto-reset, if it continues to trip.
The reset counter increases by one each time the soft starter auto-resets, and
decreases by one after each successful start/stop cycle.
NOTE
If the starter is manually reset, the resets counter will return to zero.
9C – Reset Delay Groups A&B
Range:
00:05 - 15:00 (minutes:seconds)
Default:
5 seconds
Description:
Sets the delay before resetting Group A and Group B trips.
9D – Reset Delay Group C
Range:
5 - 60 (minutes)
Default:
5 minutes
Description:
Sets the delay before resetting Group C trips.
8.4.10
10 Display
10A – Language
Options:
English (default)
Português
Chinese
Français
Español
Italiano
Deutsch
Russian
Description:
Selects which language the keypad will use to display messages and
feedback.
10B, 10C, 10D, 10E – User-Programmable Screen
Options:
Blank
Displays no data in the selected area, allowing long
messages to be shown without overlapping.
Starter State
The starter's operating state (starting, running, stopping
or tripped). Only available for top left and bottom left
positions on the screen.
Motor Current
The average current measured on three phases.
Motor pf
The motor's power factor, measured by the soft starter.
Mains Frequency
The average frequency measured on three phases.
Motor kW
The motor's running power in kilowatts.
Motor HP
The motor's running power in horsepower.
Motor Temp
The motor's temperature, calculated by the thermal
model.
kWh
The number of kilowatt hours the motor has run via the
soft starter.
Hours Run
The number of hours the motor has run via the soft
starter.
Description:
Selects which information will be displayed on the programmable monitoring
screen.
•
10B
User Screen - Top Left
Default:
Starter State