ASTAT XL User Manual
Fout! Stijl niet gedefinieerd.
10
DET-812
4.2.2
Current Ratings for Continuous Operation (Not bypassed)
351 A : AC-53a
3.5 - 15 : 50 -
6
Starts per hour
On-load duty cycle (%)
Start time (seconds)
Start current (multiple of motor full load current)
Starter current rating (amperes)
In-line connection
AC53a 3-10:50-6
40 ºC <1000 metres
AC53a 3.5-15:50-6
40 ºC <1000 metres
AC53a 4-20:50-6
40 ºC <1000 metres
AC53a 4.5-30:50-6
40 ºC <1000 metres
QLxxX0255D
255 A
222 A
195 A
171 A
QLxxX0360D
360 A
351 A
303 A
259 A
QLxxX0380D
380 A
380 A
348 A
292 A
QLxxX0430D
430 A
413 A
355 A
301 A
QLxxX0620D
620 A
614 A
515 A
419 A
QLxxX0650D
650 A
629 A
532 A
437 A
QLxxX0790D
790 A
790 A
694 A
567 A
QLxxX0930D
930 A
930 A
800 A
644 A
QLxxX1200D
1200 A
1200 A
1135 A
983 A
QLxxX1410D
1410 A
1355 A
1187 A
1023 A
QLxxX1600D
1600 A
1600 A
1433 A
1227 A
Inside delta connection
AC53a 3-10:50-6
40 ºC <1000 metres
AC53a 3.5-15:50-6
40 ºC <1000 metres
AC53a 4-20:50-6
40 ºC <1000 metres
AC53a 4.5-30:50-6
40 ºC <1000 metres
QLxxX0255D
382 A
334 A
293 A
257 A
QLxxX0360D
540 A
527 A
455 A
388 A
QLxxX0380D
570 A
570 A
522 A
437 A
QLxxX0430D
645 A
620 A
533 A
451 A
QLxxX0620D
930 A
920 A
773 A
628 A
QLxxX0650D
975 A
943 A
798 A
656 A
QLxxX0790D
1185 A
1185 A
1041 A
850 A
QLxxX0930D
1395 A
1395 A
1200 A
966 A
QLxxX1200D
1800 A
1800 A
1702 A
1474 A
QLxxX1410D
2115 A
2033 A
1780 A
1535 A
QLxxX1600D
2400 A
2400 A
2149 A
1840 A