ASTAT XL User Manual
Fout! Stijl niet gedefinieerd.
DET-812
39
8.3
Extended Menu
The Extended Menu provides access to all the ASTAT XL's programmable parameters.
Default Setting
1
Motor Details
1A
Motor Full Load Current
Model dependent
1B
Locked Rotor Time
00:10 mm:ss
1C
Motor FLC-2
Model dependent
1D
Locked Rotor Time-2
00:10 mm:ss
1E
Dual Thermal Model
Single
2
Primary Start/Stop
2A
Start Mode
Constant Current
2B
Current Limit
350% FLC
2C
Initial Current
350% FLC
2D
Start Ramp Time
00:10 mm:ss
2E
Kickstart Level
500% FLC
2F
Kickstart Time
0 ms
2G
Excess Start Time
00:20 mm:ss
2H
Stop Mode
Coast To Stop
2I
Stop Time
00:00 mm:ss
2J
Adaptive Start Profile
Constant Acceleration
2K
Adaptive Stop Profile
Constant Deceleration
2L
Adaptive Control Gain
75%
3
Secondary Start/Stop
3A
Start Mode-2
Constant Current
3B
Current Limit-2
350% FLC
3C
Initial Current-2
350% FLC
3D
Start Ramp-2
00:10 mm:ss
3E
Kickstart Level-2
500% FLC
3F
Kickstart Time-2
0 ms
3G
Excess Start Time-2
00:20 mm:ss
3H
Stop Mode-2
Coast To Stop
3I
Stop Time-2
00:00 mm:ss
3J
Adaptive Start Profile-2
Constant Acceleration
3K
Adaptive Stop Profile-2
Constant Deceleration
3L
Adaptive Control Gain-2
75%
4
Protection Levels
4A
Current Imbalance
30%
4B
Phase Sequence
Any Sequence
4C
Undercurrent
20% FLC
4D
Instantaneous Overcurrent
400% FLC
4E
Input A Trip
Always Active
4F
Motor Temperature Check
Do Not Check
4G
Frequency Check
Start/Run
4H
Frequency Variation
±5 Hz
5
Protection Delays
5A
Restart Delay
00:10 mm:ss
5B
Current Imbalance Delay
00:03 mm:ss
5C
Undercurrent Delay
00:05 mm:ss
5D
Instantaneous Overcurrent Delay
00:00 mm:ss
5E
Input A Trip Delay
00:00 mm:ss
5F
Input A Initial Delay
00:00 mm:ss
5G
Frequency Delay
00:01 mm:ss