ASTAT XL User Manual
Fout! Stijl niet gedefinieerd.
38
DET-812
8.2
Standard Menu
The standard menu provides access to commonly used parameters, allowing the user to configure the
ASTAT XL as required for the application.
Default Setting
1
Motor Details
1A
Motor Full Load Current
Model dependent
2
Primary Start/Stop
2A
Start Mode
Constant Current
2B
Current Limit
350%
2C
Initial Current
350%
2D
Start Ramp Time
00:10 mm:ss
2G
Excess Start Time
00:20 mm:ss
2H
Stop Mode
Coast To Stop
2I
Stop Time
00:00 mm:ss
4
Protection Levels
4B
Phase Sequence
Any Sequence
4C
Undercurrent
20% FLC
4D
Instantaneous Overcurrent
400% FLC
4E
Input A Trip
Always Active
5
Protection Delays
5C
Undercurrent Delay
00:05 mm:ss
5D
Instantaneous Overcurrent Delay
00:00 mm:ss
5E
Input A Trip Delay
00:00 mm:ss
5F
Input A Initial Delay
00:00 mm:ss
6
Inputs
6D
Input A Function
Motor Set Select
6E
Input A Name
Input Trip
7
Relay Outputs
7A
Relay A Function
Main Contactor
7B
Relay A On Delay
00:00 mm:ss
7C
Relay A Off Delay
00:00 mm:ss
7D
Relay B Function
Run
7E
Relay B On Delay
00:00 mm:ss
7F
Relay B Off Delay
00:00 mm:ss
7G
Relay C Function
Trip
7H
Relay C On Delay
00:00 mm:ss
7I
Relay C Off Delay
00:00 mm:ss
7J
Low Current Flag
50% FLC
7K
High Current Flag
100% FLC
7L
Motor Temperature Flag
80% FLC
10
Display
10A
Language
English
10B
User Screen - Top Left
Starter State
10C
User Screen - Top Right
Blank
10D
User Screen - Bottom Left
Hours Run
10E
User Screen - Bottom Right
Blank
10J
Display A or kW
Current