ASTAT XL User Manual
Fout! Stijl niet gedefinieerd.
44
DET-812
Description:
Sets the total start time for an Adaptive Control start or the ramp time for
current ramp starting (from the initial current to the current limit).
3E – Kickstart Level-2
Range:
100% - 700% FLC
Default:
500%
Description:
Sets the level of the kickstart current.
3F – Kickstart Time-2
Range:
0 - 2000 (milliseconds)
Default:
0000 milliseconds
Description:
Sets the kickstart duration. A setting of 0 disables kickstart.
3G – Excess Start Time-2
Range:
0:00 - 4:00 (minutes:seconds)
Default:
20 seconds
Description:
Set as required.
3H – Stop Mode-2
Options:
Coast To Stop (default)
TVR Soft Stop
Adaptive Control
Brake
Description:
Selects the stop mode.
3I – Stop Time-2
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets the stop time.
3J – Adaptive Start Profile-2
Options:
Early Acceleration
Constant Acceleration (default)
Late Acceleration
Description:
Selects which profile the ASTAT XL will use for an Adaptive Control soft start.
3K – Adaptive Stop Profile-2
Options:
Early Deceleration
Constant Deceleration (default)
Late Deceleration
Description:
Selects which profile the ASTAT XL will use for an Adaptive Control soft stop.
3L – Adaptive Control Gain-2
Range:
1% - 200%
Default:
75%
Description:
Adjusts the performance of Adaptive Control. This setting affects both
starting and stopping control.
8.4.4
4 Protection Levels
4A – Current Imbalance
Range:
10% - 50%
Default:
30%
Description:
Sets the trip point for current imbalance protection.
4B – Phase Sequence
Options:
Any Sequence (default)
Positive Only
Negative Only
Description:
Selects which phase sequences the soft starter will allow at a start. During
its pre-start checks, the starter examines the sequence of the phases at its