ASTAT XL User Manual
Fout! Stijl niet gedefinieerd.
40
DET-812
Default Setting
6
Inputs
6A
Local/Remote
LCL/RMT Anytime
6B
Comms in Remote
Enable Control in RMT
6C
Remote Reset Logic
Normally Closed (N/C)
6D
Input A Function
Motor Set Select
6E
Input A Name
Input Trip
7
Relay Outputs
7A
Relay A Function
Main Contactor
7B
Relay A On Delay
00:00 mm:ss
7C
Relay A Off Delay
00:00 mm:ss
7D
Relay B Function
Run
7E
Relay B On Delay
00:00 mm:ss
7F
Relay B Off Delay
00:00 mm:ss
7G
Relay C Function
Trip
7H
Relay C On Delay
00:00 mm:ss
7I
Relay C Off Delay
00:00 mm:ss
7J
Low Current Flag
50% FLC
7K
High Current Flag
100% FLC
7L
Motor Temperature Flag
80%
8
Analog Output
8A
Analog Output A
Current (% FLC)
8B
Analog A Scale
4-20 mA
8C
Analog A Maximum Adjustment
100%
8D
Analog A Minimum Adjustment
0%
9
Auto-Reset
9A
Auto-Reset Action
Do Not Auto-Reset
9B
Maximum Resets
1
9C
Reset Delay Groups A&B
00:05 mm:ss
9D
Reset Delay Group C
5 minutes
10
Display
10A
Language
English
10B
User Screen - Top Left
Starter State
10C
User Screen - Top Right
Blank
10D
User Screen - Bottom Left
Hours Run
10E
User Screen - Bottom Right
Blank
10F
Graph Timebase
10 seconds
10G
Graph Maximum Adjustment
400%
10H
Graph Minimum Adjustment
0%
10I
Mains Reference Voltage
400 V
10J
Display A or kW
Current
15
Restricted
15A
Access Code
0000
15B
Adjustment Lock
Read & Write
15C
Emergency Run
Disable
15D
Current Calibration
100%
15E
Shorted SCR Action
3-Phase Control Only
15F
Jog Torque
50%
15G
Brake Torque
20%
15H
Brake Time
00:01 mm:ss
15I
Brake Torque-2
20%