6.2.24 XC-## Ext. PID Closed Loop
Par. No. # Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion
index
Type
XC-0#
XC-00
Closed Loop Type
[0] Auto
2 set-ups
TRUE
-
Uint8
XC-01
PID Performance
[0] Normal
2 set-ups
TRUE
-
Uint8
XC-02
PID Output Change
0.10 N/A
2 set-ups
TRUE
-2
Uint16
XC-03
Minimum Feedback Level
-999999.000 N/A
2 set-ups
TRUE
-3
Int32
XC-04
Maximum Feedback Level
999999.000 N/A
2 set-ups
TRUE
-3
Int32
XC-09
PID Autotuning
[0] Disabled
All set-ups
TRUE
-
Uint8
XC-1#
XC-10
Ext. 1 Ref./Feedback Unit
[1] %
All set-ups
TRUE
-
Uint8
XC-11
Ext. 1 Minimum Reference
0.000 ExtPID1Unit
All set-ups
TRUE
-3
Int32
XC-12
Ext. 1 Maximum Reference
100.000 ExtPID1Unit
All set-ups
TRUE
-3
Int32
XC-13
Ext. 1 Reference Source
[0] No function
All set-ups
TRUE
-
Uint8
XC-14
Ext. 1 Feedback Source
[0] No function
All set-ups
TRUE
-
Uint8
XC-15
Ext. 1 Setpoint
0.000 ExtPID1Unit
All set-ups
TRUE
-3
Int32
XC-17
Ext. 1 Reference [Unit]
0.000 ExtPID1Unit
All set-ups
TRUE
-3
Int32
XC-18
Ext. 1 Feedback [Unit]
0.000 ExtPID1Unit
All set-ups
TRUE
-3
Int32
XC-19
Ext. 1 Output [%]
0 %
All set-ups
TRUE
0
Int32
XC-2#
XC-20
Ext. 1 Normal/Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
XC-21
Ext. 1 Proportional Gain
0.01 N/A
All set-ups
TRUE
-2
Uint16
XC-22
Ext. 1 Integral Time
10000.00 s
All set-ups
TRUE
-2
Uint32
XC-23
Ext. 1 Differentation Time
0.00 s
All set-ups
TRUE
-2
Uint16
XC-24
Ext. 1 Dif. Gain Limit
5.0 N/A
All set-ups
TRUE
-1
Uint16
XC-3#
XC-30
Ext. 2 Ref./Feedback Unit
[1] %
All set-ups
TRUE
-
Uint8
XC-31
Ext. 2 Minimum Reference
0.000 ExtPID2Unit
All set-ups
TRUE
-3
Int32
XC-32
Ext. 2 Maximum Reference
100.000 ExtPID2Unit
All set-ups
TRUE
-3
Int32
XC-33
Ext. 2 Reference Source
[0] No function
All set-ups
TRUE
-
Uint8
XC-34
Ext. 2 Feedback Source
[0] No function
All set-ups
TRUE
-
Uint8
XC-35
Ext. 2 Setpoint
0.000 ExtPID2Unit
All set-ups
TRUE
-3
Int32
XC-37
Ext. 2 Reference [Unit]
0.000 ExtPID2Unit
All set-ups
TRUE
-3
Int32
XC-38
Ext. 2 Feedback [Unit]
0.000 ExtPID2Unit
All set-ups
TRUE
-3
Int32
XC-39
Ext. 2 Output [%]
0 %
All set-ups
TRUE
0
Int32
XC-4#
XC-40
Ext. 2 Normal/Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
XC-41
Ext. 2 Proportional Gain
0.01 N/A
All set-ups
TRUE
-2
Uint16
XC-42
Ext. 2 Integral Time
10000.00 s
All set-ups
TRUE
-2
Uint32
XC-43
Ext. 2 Differentation Time
0.00 s
All set-ups
TRUE
-2
Uint16
XC-44
Ext. 2 Dif. Gain Limit
5.0 N/A
All set-ups
TRUE
-1
Uint16
XC-5#
XC-50
Ext. 3 Ref./Feedback Unit
[1] %
All set-ups
TRUE
-
Uint8
XC-51
Ext. 3 Minimum Reference
0.000 ExtPID3Unit
All set-ups
TRUE
-3
Int32
XC-52
Ext. 3 Maximum Reference
100.000 ExtPID3Unit
All set-ups
TRUE
-3
Int32
XC-53
Ext. 3 Reference Source
[0] No function
All set-ups
TRUE
-
Uint8
XC-54
Ext. 3 Feedback Source
[0] No function
All set-ups
TRUE
-
Uint8
XC-55
Ext. 3 Setpoint
0.000 ExtPID3Unit
All set-ups
TRUE
-3
Int32
XC-57
Ext. 3 Reference [Unit]
0.000 ExtPID3Unit
All set-ups
TRUE
-3
Int32
XC-58
Ext. 3 Feedback [Unit]
0.000 ExtPID3Unit
All set-ups
TRUE
-3
Int32
XC-59
Ext. 3 Output [%]
0 %
All set-ups
TRUE
0
Int32
How to Program
AF-600 FP High Power Operating Instructions
108
6
6