3.1.15 NEC and UL Compliance
Fuses or Circuit Breakers are mandatory to comply with NEC 2009. We recommend using a selection of the following
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 600V
depending on the drive voltage rating. With the proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
Recommended max. fuse
AF-600 1-
phase
Power
AF-600 3-
phase
Power
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
HP
HP
Type RK1
1)
Type J
Type T
Type CC
Type CC
Type CC
1
KTN-R-10
JKS-10
JJN-10
FNQ-R-10
KTK-R-10
LP-CC-10
2
KTN-R-15
JKS-15
JJN-15
FNQ-R-15
KTK-R-15
LP-CC-15
2
3
KTN-R-20
JKS-20
JJN-20
FNQ-R-20
KTK-R-20
LP-CC-20
3
5
KTN-R-30
JKS-30
JJN-30
FNQ-R-30
KTK-R-30
LP-CC-30
5
7.5-10
KTN-R-50
KS-50
JJN-50
-
-
-
7.5
15
KTN-R-60
JKS-60
JJN-60
-
-
-
10
20
KTN-R-80
JKS-80
JJN-80
-
-
-
25-30
KTN-R-125
JKS-125
JJN-125
-
-
-
20
40
KTN-R-150
JKS-150
JJN-150
-
-
-
30
50
KTN-R-200
JKS-200
JJN-200
-
-
-
60
KTN-R-250
JKS-250
JJN-250
-
-
-
Table 3.8 200-240V
Recommended max. fuse
AF-600 1-
phase
Power
AF-600 3-
phase
Power
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
HP
HP
Type RK1
Type RK1
Type CC
Type RK1
3)
1
5017906-010
KLN-R-10
ATM-R-10
A2K-10-R
2
5017906-016
KLN-R-15
ATM-R-15
A2K-15-R
2
3
5017906-020
KLN-R-20
ATM-R-20
A2K-20-R
3
5
5012406-032
KLN-R-30
ATM-R-30
A2K-30-R
5
7.5-10
5014006-050
KLN-R-50
-
A2K-50-R
7.5
15
5014006-063
KLN-R-60
-
A2K-60-R
10
20
5014006-080
KLN-R-80
-
A2K-80-R
25-30
2028220-125
KLN-R-125
-
A2K-125-R
20
40
2028220-150
KLN-R-150
-
A2K-150-R
30
50
2028220-200
KLN-R-200
-
A2K-200-R
60
2028220-250
KLN-R-250
-
A2K-250-R
Table 3.9 200-240V
Electrical Installation
AF-600 FP High Power Operating Instructions
25
3
3
Содержание AF-600 FP Series
Страница 44: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 43 4 4...
Страница 45: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 44 4 4...
Страница 46: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 45 4 4...