Mains Supply 3 x 380 - 480 VAC
Typical Shaft output at
400 V [kW]
500
560
630
710
800
1000
Typical Shaft output at
460 V [HP]
650
750
900
1000
1200
1350
Unit Size IP21, 54
without/ with options
cabinet
61/63
61/63
61/63
61/63
62/64
62/64
Output current
Continuous
(at 400 V) [A]
880
990
1120
1260
1460
1720
Intermittent (60 sec
overload)
(at 400 V) [A]
968
1089
1232
1386
1606
1892
Continuous
(at 460 V) [A]
780
890
1050
1160
1380
1530
Intermittent (60 sec
overload)
(at 460 V) [A]
858
979
1155
1276
1518
1683
Continuous KVA
(at 400 V) [KVA]
610
686
776
873
1012
1192
Continuous KVA
(at 460 V) [KVA]
621
709
837
924
1100
1219
Max. input current
Continuous
(at 400 V ) [A]
857
964
1090
1227
1422
1675
Continuous (at 460 V)
[A]
759
867
1022
1129
1344
1490
Max. cable size,motor
[mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size,mains
[mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size,
loadsharing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. external pre-fuses
[A]
1
1600
2000
2500
Estimated power loss
at rated max. load [W]
4)
Weight,
enclosure IP21, IP 54
[kg]
1004/ 1299
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
Weight Rectifier Module
[kg]
102
102
102
102
136
136
Weight Inverter Module
[kg]
102
102
102
136
102
102
Efficiency
4)
0.98
Output frequency
0-600 Hz
Heatsink overtemp. trip
95
°
C
Power card ambient trip
68
°
C
General Specifications
AF-600 FP High Power Operating Instructions
119
7
7
Содержание AF-600 FP Series
Страница 44: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 43 4 4...
Страница 45: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 44 4 4...
Страница 46: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 45 4 4...