6.2.23 CL-## PID Closed Loop
Par. No. # Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion
index
Type
CL-0#
CL-00
Feedback 1 Source
[2] Analog input 54
All set-ups
TRUE
-
Uint8
CL-01
Feedback 1 Conversion
[0] Linear
All set-ups
FALSE
-
Uint8
CL-02
Feedback 1 Source Unit
null
All set-ups
TRUE
-
Uint8
CL-03
Feedback 2 Source
[0] No function
All set-ups
TRUE
-
Uint8
CL-04
Feedback 2 Conversion
[0] Linear
All set-ups
FALSE
-
Uint8
CL-05
Feedback 2 Source Unit
null
All set-ups
TRUE
-
Uint8
CL-06
Feedback 3 Source
[0] No function
All set-ups
TRUE
-
Uint8
CL-07
Feedback 3 Conversion
[0] Linear
All set-ups
FALSE
-
Uint8
CL-08
Feedback 3 Source Unit
null
All set-ups
TRUE
-
Uint8
CL-1#
CL-12
Reference/Feedback Unit
null
All set-ups
TRUE
-
Uint8
CL-13
Minimum Reference/Feedb.
0.000 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
CL-14
Maximum Reference/Feedb.
100.000 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
CL-2#
CL-20
Feedback Function
[3] Minimum
All set-ups
TRUE
-
Uint8
CL-21
Setpoint 1
0.000 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
CL-22
Setpoint 2
0.000 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
CL-23
Setpoint 3
0.000 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
CL-3#
CL-30
Refrigerant
[0] R22
All set-ups
TRUE
-
Uint8
CL-31
User Defined Refrigerant A1
10.0000 N/A
All set-ups
TRUE
-4
Uint32
CL-32
User Defined Refrigerant A2
-2250.00 N/A
All set-ups
TRUE
-2
Int32
CL-33
User Defined Refrigerant A3
250.000 N/A
All set-ups
TRUE
-3
Uint32
CL-34
Duct 1 Area [m2]
0.500 m2
All set-ups
TRUE
-3
Uint32
CL-35
Duct 1 Area [in2]
750 in2
All set-ups
TRUE
0
Uint32
CL-36
Duct 2 Area [m2]
0.500 m2
All set-ups
TRUE
-3
Uint32
CL-37
Duct 2 Area [in2]
750 in2
All set-ups
TRUE
0
Uint32
CL-38
Air Density Factor [%]
100 %
All set-ups
TRUE
0
Uint32
CL-7#
CL-70
Closed Loop Type
[0] Auto
2 set-ups
TRUE
-
Uint8
CL-71
PID Performance
[0] Normal
2 set-ups
TRUE
-
Uint8
CL-72
PID Output Change
0.10 N/A
2 set-ups
TRUE
-2
Uint16
CL-73
Minimum Feedback Level
-999999.000 ProcessCtrlUnit
2 set-ups
TRUE
-3
Int32
CL-74
Maximum Feedback Level
999999.000 ProcessCtrlUnit
2 set-ups
TRUE
-3
Int32
CL-79
PID Autotuning
[0] Disabled
All set-ups
TRUE
-
Uint8
CL-8#
CL-81
PID Normal/ Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
CL-82
PID Start Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
CL-83
PID Start Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
CL-84
On Reference Bandwidth
5 %
All set-ups
TRUE
0
Uint8
CL-9#
CL-91
PID Anti Windup
[1] On
All set-ups
TRUE
-
Uint8
CL-93
PID Proportional Gain
0.50 N/A
All set-ups
TRUE
-2
Uint16
CL-94
PID Integral Time
20.00 s
All set-ups
TRUE
-2
Uint32
CL-95
PID Differentiation Time
0.00 s
All set-ups
TRUE
-2
Uint16
CL-96
PID Diff. Gain Limit
5.0 N/A
All set-ups
TRUE
-1
Uint16
How to Program
AF-600 FP High Power Operating Instructions
107
6
6