3.2 Connection
Examples
3.2.1 Start/Stop
Terminal 18 =
E-01 Terminal 18 Digital Input
[8]
Start
Terminal 27 =
E-03 Terminal 27 Digital Input
[0]
No
operation
(Default
coast inverse
)
3.2.2 Pulse Start/Stop
Terminal 18 =
E-01 Terminal 18 Digital Input
[9]
Latched
start
Terminal 27=
E-03 Terminal 27 Digital Input
[6]
Stop inverse
3.2.3 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 =
E-01 Terminal 18 Digital Input
Start
[9] (default)
Terminal 27 =
E-03 Terminal 27 Digital Input
Freeze reference [19]
Terminal 29 =
E-04 Terminal 29 Digital Input
Speed up [21]
Terminal 32 =
E-05 Terminal 32 Digital Input
Speed down [22]
3.2.4 Potentiometer Reference
Voltage reference via a potentiometer
Reference Source 1 = [1]
Analog input 53
(default)
Terminal 53, Low Voltage = 0V
Terminal 53, High Voltage = 10V
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)
Electrical Installation
AF-600 FP High Power Operating Instructions
34
3
3