Mains Supply 3 x 525 - 690 VAC
Typical Shaft output at 550
V [kW]
560
670
750
850
1000
Typical Shaft output at 575
V [HP]
750
950
1050
1150
1350
Unit Size IP21, 54 without/
with options cabinet
61/ 63
61/ 63
61/ 63
62/ 64
62/ 64
Output current
Continuous
(at 550 V) [A]
763
889
988
1108
1317
Intermittent (60 sec
overload)
(at 550 V) [A]
839
978
1087
1219
1449
Continuous
(at 575/690 V) [A]
730
850
945
1060
1260
Intermittent (60 sec
overload)
(at 575/690 V) [A]
803
935
1040
1166
1386
Continuous KVA
(at 550 V) [KVA]
727
847
941
1056
1255
Continuous KVA
(at 575 V) [KVA]
727
847
941
1056
1255
Continuous KVA
(at 690 V) [KVA]
872
1016
1129
1267
1506
Max. input current
Continuous
(at 550 V ) [A]
743
866
962
1079
1282
Continuous
(at 575 V) [A]
711
828
920
1032
1227
Continuous
(at 690 V) [A]
711
828
920
1032
1227
Max. cable size,motor
[mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size,mains
[mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size,
loadsharing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. external pre-fuses [A]
1
1600
2000
Estimated power loss
at rated max. load [W]
4)
Weight,
Unit Size IP21, IP 54 [kg]
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
Weight, Rectifier Module
[kg]
102
102
102
136
136
Weight, Inverter Module
[kg]
102
102
136
102
102
Efficiency
4)
0.98
Output frequency
0-500 Hz
Heatsink overtemp. trip
85
°
C
Power card ambient trip
68
°
C
1) For type of fuse see section
Fuses.
2) American Wire Gauge.
General Specifications
AF-600 FP High Power Operating Instructions
123
7
7
Содержание AF-600 FP Series
Страница 44: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 43 4 4...
Страница 45: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 44 4 4...
Страница 46: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 45 4 4...