6.2.25 PC-## Pump Controller
Par. No. # Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
PC-0#
PC-00
Pump Controller
[0] Disabled
2 set-ups
FALSE
-
Uint8
PC-02
Motor Start
[0] Direct on Line
2 set-ups
FALSE
-
Uint8
PC-04
Pump Cycling
[0] Disabled
All set-ups
TRUE
-
Uint8
PC-05
Fixed Lead Pump
[1] Yes
2 set-ups
FALSE
-
Uint8
PC-06
Number of Pumps
2 N/A
2 set-ups
FALSE
0
Uint8
PC-1#
PC-10
Minimum Run Time Override
[0] Disabled
All set-ups
FALSE
-
Uint8
PC-11
Minimum Run Time Override Value
0.000 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
PC-2#
PC-20
Staging Bandwidth
10 %
All set-ups
TRUE
0
Uint8
PC-21
Override Bandwidth
100 %
All set-ups
TRUE
0
Uint8
PC-22
Fixed Speed Bandwidth
casco_staging_bandwidth
(P2520)
All set-ups
TRUE
0
Uint8
PC-23
SBW Staging Delay
15 s
All set-ups
TRUE
0
Uint16
PC-24
SBW Destaging Delay
15 s
All set-ups
TRUE
0
Uint16
PC-25
OBW Time
10 s
All set-ups
TRUE
0
Uint16
PC-26
Destage At No-Flow
[0] Disabled
All set-ups
TRUE
-
Uint8
PC-27
Stage Function
[1] Enabled
All set-ups
TRUE
-
Uint8
PC-28
Stage Function Time
15 s
All set-ups
TRUE
0
Uint16
PC-29
Destage Function
[1] Enabled
All set-ups
TRUE
-
Uint8
PC-3#
PC-30
Destage Function Time
15 s
All set-ups
TRUE
0
Uint16
PC-4#
PC-40
Decel Ramp Delay
10.0 s
All set-ups
TRUE
-1
Uint16
PC-41
Accel Ramp Delay
2.0 s
All set-ups
TRUE
-1
Uint16
PC-42
Staging Threshold
ExpressionLimit
All set-ups
TRUE
0
Uint8
PC-43
Destaging Threshold
ExpressionLimit
All set-ups
TRUE
0
Uint8
PC-44
Staging Speed [RPM]
0 RPM
All set-ups
TRUE
67
Uint16
PC-45
Staging Speed [Hz]
0.0 Hz
All set-ups
TRUE
-1
Uint16
PC-46
Destaging Speed [RPM]
0 RPM
All set-ups
TRUE
67
Uint16
PC-47
Destaging Speed [Hz]
0.0 Hz
All set-ups
TRUE
-1
Uint16
PC-5#
PC-50
Lead Pump Alternation
[0] Off
All set-ups
TRUE
-
Uint8
PC-51
Alternation Event
[0] External
All set-ups
TRUE
-
Uint8
PC-52
Alternation Time Interval
24 h
All set-ups
TRUE
74
Uint16
PC-53
Alternation Timer Value
0 N/A
All set-ups
TRUE
0
VisStr[7]
PC-54
Alternation Predefined Time
ExpressionLimit
All set-ups
TRUE
0
TimeOfDay-
WoDate
PC-55
Alternate if Load < 50%
[1] Enabled
All set-ups
TRUE
-
Uint8
PC-56
Staging Mode at Alternation
[0] Slow
All set-ups
TRUE
-
Uint8
PC-58
Run Next Pump Delay
0.1 s
All set-ups
TRUE
-1
Uint16
PC-59
Run on Line Delay
0.5 s
All set-ups
TRUE
-1
Uint16
PC-8#
PC-80
Pump Status
0 N/A
All set-ups
TRUE
0
VisStr[25]
PC-81
Pump Status
0 N/A
All set-ups
TRUE
0
VisStr[25]
PC-82
Lead Pump
0 N/A
All set-ups
TRUE
0
Uint8
PC-83
Relay Status
0 N/A
All set-ups
TRUE
0
VisStr[4]
PC-84
Pump ON Time
0 h
All set-ups
TRUE
74
Uint32
How to Program
AF-600 FP High Power Operating Instructions
110
6
6
Содержание AF-600 FP Series
Страница 44: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 43 4 4...
Страница 45: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 44 4 4...
Страница 46: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 45 4 4...