CHAPTER 1: INTRODUCTION
SPECIFICATIONS
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
1–31
REMOTE MODBUS DEVICE PROFILE
Device Name:........................................................BSG3 (13 alphanumeric characters maximum)
IP Address:..............................................................0.0.0.0 – standard Ethernet address
Slave Address: ......................................................254 (1 to 254)
Modbus Port:.........................................................502 (0 to 10000, default 502)
Poll Rate: .................................................................3 minute (OFF, 3 to 120 minutes), the continuous mode poll
interval is defined as the poll rate interval
Trigger:.....................................................................Off (any FlexLogic Operand), the trigger mode is based on
the FlexLogic operand designed to trigger the poll
Testing & Certification
APPROVALS
Applicable Council Directive
According to
CE compliance
Low voltage directive
EN60255-27
EMC Directive
EN60255-26
R&TTE Directive
ETSI EN300 328 ETSI EN301 489-1 ETSI
EN301-489-17
North America
cULus
UL508, e57838 NKCR, NRGU
C22.2.No 14, e57838 NKCR7, NRGU7
ISO
Manufactured under a registered
quality program
ISO9001
TESTING AND CERTIFICATION
Test
Reference Standard
Test Level
Dielectric voltage withstand
EN60255-5/IEC60255-27
2.3 kV
Impulse voltage withstand
EN60255-5/IEC60255-27
5 kV
Insulation resistance
IEC60255-27
500 VDC
Damped Oscillatory
IEC61000-4-18
2.5 kV CM, 1 kV DM, 1 MHz
Electrostatic Discharge
EN61000-4-2
Level 4
RF immunity
EN61000-4-3
Level 3
Fast Transient Disturbance
EN61000-4-4
Class A and B
Surge Immunity
EN61000-4-5
Level 3
Conducted RF Immunity
EN61000-4-6
Level 3
Power Frequency Immunity
IEC60255-26
Class A & B
Voltage variation, interruption and
Ripple DC
IEC60255-26
PQT levels based on
IEC61000-4-29,
IEC61000-4-11 and
IEC61000-4-17
Radiated & Conducted Emissions CISPR11 /CISPR22
Class A
Sinusoidal Vibration
IEC60255-21-1
Class 1
Shock & Bump
IEC60255-21-2
Class 1
Seismic
IEC60255-21-3
Class 2
Power magnetic Immunity
IEC61000-4-8
Level 5
Pulse Magnetic Immunity
IEC61000-4-9
Level 4
Damped Magnetic Immunity
IEC61000-4-10
Level 4
Voltage Dip & interruption
IEC61000-4-11
0, 40, 70, 80% dips,
250/300 cycle interrupts
Содержание 869
Страница 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 48: ...1 38 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION ...
Страница 78: ...2 30 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ELECTRICAL INSTALLATION CHAPTER 2 INSTALLATION ...
Страница 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Страница 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Страница 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Страница 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...