4–292
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING
CHAPTER 4: SETPOINTS
STATOR FAULT PKP DELAY 1(2)
Range: 5 to 60 min in steps of 5 min
Default: 15 min
Configure the delay in minutes after which the bearing fault operand pickup level 1 (level
2) will operate if the level sustains.
BLOCK
Range: Off, FlexLogic operands
Default: Off
The Stator Inter-Turn fault element is blocked, when the selected operand is asserted.
OUTPUT RELAY X
For details see
EVENTS
Range: Enabled, Disabled
Default: Enabled
The selection of the
Enabled
setting enables the events of the Stator Inter-Turn fault
function.
TARGETS
Range: Self-reset, Latched, Disabled
Default: Latched
The selection of the
Self-reset
or
Latched
setting enables the targets of the Stator Inter-
Turn fault function.
NOTE
NOTE:
In cases where baseline mode is disabled or baseline data is not available, the PKP related
settings of bearing, mechanical and stator for dB levels should correspond to peak
magnitude and not change in dB magnitude (Example: a default of 75dB for Flt PKP Stg 1
and 65dB for Flt PKP Stg 2).
Содержание 869
Страница 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 48: ...1 38 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION ...
Страница 78: ...2 30 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ELECTRICAL INSTALLATION CHAPTER 2 INSTALLATION ...
Страница 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Страница 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Страница 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Страница 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...