CHAPTER 3: INTERFACES
FRONT CONTROL PANEL INTERFACE
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
3–11
NOTE
NOTE:
Do not remove power from the relay whenever the Settings Save icon is ON. When power
is removed the data being saved can also be lost.
Table 3-7: Local Mode Icon
Relay Messages
Target Messages
Targets are messages displayed on the screen when any change of state of protection,
control, monitoring, or digital signal takes place. For the user’s convenience, the targets for
major motor protection elements are set to Latched by default. The user can disable
targets for any particular element by selecting and entering the setting “Disabled” within
the element’s menu.
Target Messages are displayed in order of their activation, whereas in cases of
simultaneous activation, they are displayed in the order outlined below (from highest to
lowest priority):
1.
Targets generated by pressing programmable pushbutton
2.
Targets generated by Contact inputs
3.
Targets generated by Protection, Control and Monitoring elements
4.
Targets generated by communications.
In cases where the Pickup and Operate flags from an element are detected at the same
time, the Pickup flag is not displayed. The Operate flag is displayed instead.
LED #6, from the first column of LEDs, is factory configured to be triggered by the
FlexLogic operand ANY TARGET, to indicate the presence of at least one target message.
This LED is labeled as “MESSAGE”. The LED can be programmed to any other FlexLogic
operand by choice.
MESSAGE TIMEOUT
:
The timeout applies to each screen that is different than the default screen to which the
user navigates. Examples include viewing, metering, or navigating to a screen with setting,
etc. If no further navigation is performed, no pushbutton is touched, and/or no target is
initiated for the time specified in the message timeout setpoint, the display goes back to
the default screen (the metering summary screen).
The target message interrupts the message timeout. It overrides it. The message timeout
starts timing after each target message, and if no more activity is recorded for the
specified time, the display goes back to the default screen.
Pressing a programmable pushbutton activates a new screen with a Target Message
corresponding to the programmed PB action. The PB Target Message is displayed for 10
seconds then defaults to the screen that was displayed before pressing the pushbutton.
The PB Target Message is recorded in the list with other generated Target Messages.
Target Messages can be cleared either by pressing the PB corresponding to the tab
“CLEAR”, or by initiating a RESET command. The “CLEAR” command clears only the Target
Messages, while initiating a RESET clears not only the Target Messages, but also any
latched LEDs and output relays.
Description
Indicates that Local Mode is active. During Local Mode, the control for the breakers and disconnect
switches can be performed only by the relay front panel.
Содержание 869
Страница 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 48: ...1 38 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION ...
Страница 78: ...2 30 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ELECTRICAL INSTALLATION CHAPTER 2 INSTALLATION ...
Страница 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Страница 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Страница 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Страница 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...