6–20
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
ARC FLASH
CHAPTER 6: METERING
Arc Flash
Path
:
Metering > Arc Flash > Arc Flash 1
HS Phase Current A/B/C
Range: 0.00 to 120000.00 A in steps of 0.01
HS Ground Current
Range: 0.00 to 120000.00 A in steps of 0.01
RTDs
Path
:
Metering > RTDs
NOTE
NOTE:
The Temperature can be displayed in Celsius or Fahrenheit degrees. The selection is made
in
Setpoints > Device > Installation > Temperature Display
.
Hottest Stator RTD #
Range: 1 to 13
Hottest Stator RTD Temp
Range: -40 to 250°C
This value shows the hottest RTD temperature from the group of RTDs when setpoint
Application is programmed as Stator. The other conditions to display this value are: RTD
n must not be Disabled (both Trip and Alarm functions) and must not be detected
Shorted or Open RTD.
Hottest Bearing RTD #
Range: 1 to 13
Hottest Bearing RTD Temp
Range: -40 to 250°C
This value shows the hottest RTD temperature from the group of RTDs when setpoint
Application is programmed as Bearing.
RTD 1(13)
Range: -40 to 250°C (temperatures < -40°C are displayed as “Shorted” and temperatures >
250°C are displayed as “Open RTD”)
Содержание 869
Страница 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 48: ...1 38 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION ...
Страница 78: ...2 30 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ELECTRICAL INSTALLATION CHAPTER 2 INSTALLATION ...
Страница 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Страница 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Страница 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Страница 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...