ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
Page 72
REV 11 (ISS 08/03/2010)
Points: global settings: editing
This menu provides the ability to simultaneously programme a set of attributes for a group of
point addresses as follows.
The menu path is: Points/Global Settings/Editing.
After programming globally with this menu, individual devices that need different attributes can
be changed in the Points menu. Scroll point addresses. The edit options available for each
address are provided in Table 15.
Table 15: Point addresses edit options
Address attribute
Remarks
Sensor sensitivity
High, medium, standard, low
Fire AVF (Alarm Verification
Function)
Enabled or disabled
Fault AVF (Alarm Verification
Function)
Enabled or disabled (Note: Global only)
Sounder base
Present or not
Detector self-test
Enabled or disabled
Points: accept points
Selecting this menu instructs the panel to carry out a self-learning process, to accept all current
devices attached to the Z-loops, or peripheral boards, as the current system configuration. The
panel displays the message "Accepting points..." and counts down to zero (0). On completion, the
panel displays "Calibrating...". If a device was not accepted, it is shown as "unaccepted".
The menu path is: Setup/Points/Accept Points.
Sounders
This menu provides the tools for setting up system sounders. Loop devices and panel outputs that
operate sounders must be defined as such to the panel to ensure that they behave correctly.
The menu path is: Setup/Sounders or Setup/Pnts/INDN. The available sounder setup options are
provided in Table 16.
Table 16: Sounder setup options
Option Description
View SAB
View which Z-loop sensors have been defined as having a sounder base (SAB). The point
address of the first sensor is displayed, plus the total number of sounder bases. Scroll to
view the list.
Edit SAB
Define which sensors have a sounder base. Add or delete a point address.
View mapped
Sounders
View of all outputs (Z-loop and panel outputs), which have been defined as sounders in
the I/O mapping tables. Scroll to view the list.
Edit mapped sounders
Define which outputs are sounders. The point address of the first sounder is displayed,
plus the total number sounders in the list. Scroll to view the list. Addresses can de added
to or deleted from the list.
Содержание ZP3
Страница 1: ...GE Security ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual ...
Страница 44: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 32 REV 11 ISS 08 03 2010 ...
Страница 56: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 44 REV 11 ISS 08 03 2010 ...
Страница 142: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 130 REV 11 ISS 08 03 2010 ...
Страница 143: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual REV 11 ISS 08 03 2010 Page 131 ...
Страница 144: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 132 REV 11 ISS 08 03 2010 ...